Advanced Setup Table
cont. next page
Df = Factory Default Setting
Step# Description Pg# Range Df
1 Prog Mode 24 Non, 1 Day, 5/2 Day, 7 Day 7
2 Available Modes 24 Heat/Cool/Auto/Off, Heat/Cool Heat/Cool
/Off, Heat/Off, Cool/Off /Auto/Off
3 Backlight 16 On, Off Off
4 Backlight Level 16 Off thru 7 levels of brightness Level 5
5 Night Dimmer 16 On/Off Off
6 Night Dimmer Brightness 16 Off thru 7 levels of brightness 2 (20%)
7 Night Dimmer Start Time 16 12A-12A 8:00P
8 Night Dimmer Stop Time 16 12A-12A 6:00A
9 Current Service Filter Runtime Hours 20 0-1999 Hours 0
10 Current Service Filter Calendar Days 20 0-720 Days 0
11 Current UV Lamp Calendar Days 21 0-720 Days 0
12 Set Service Filter Runtime Hours 20 0-1950 hours 0
13 Set Service Filter Calendar Days 20 0-720 Days 0
14 Set UV Lamp Calendar Days 21 0-720 Days 0
15 Language 16 English, Espanol, Francais English
16 Scrolling Method 17 “L-R Slow, L-R Fast, Word L-R “Whole
Slow, Word L-R Fast, Whole Words
Word L Slow, Whole Word Center
R Slow, Whole Word Ctr. Fast, Fast”
Whole Word Ctr. Slow”
17 Setpoint Limits 25 No, Use No
18 Max Heat Setpoint 25 35 - 99 Degrees 74
19 Min Cool Setpoint 25 35 - 99 Degrees 70
20 Cycles Per Hour 25 No Limit, 2, 3, 4, 5, 6 6
21 Compressor Minimum Off Minutes 25 0, 3, 5 Minutes 5
22 Min. Heat/Cool Setpoint Difference 25 0 - 6 Degrees 2
23 Number of Heat Stages 25 0 - 3 2
24 Number of Cool Stages 25 0 - 2 1
25 Number Of Compressor Stages 25 1, 2 1
26 Number of Aux Stages 25 0, 1, 2 0
27 1st Stage Deadband 26 1 - 6 Degrees 2
28 2nd Stage Deadband 26 0 - 10 Degrees 2
29 3rd Stage Deadband 26 0 - 10 Degrees 2
30 4th Stage Deadband 26 0 - 10 Degrees 2
31 Minutes Between 1st and 2nd Stage 26 0 - 60 Minutes 2
32 Minutes Between 2nd and 3rd Stage 26 0 - 60 Minutes 2
33 Minutes Between 3rd and 4th Stage 26 0 - 60 Minutes 2
34 2nd StageTurnoff Point 26 Deadband, Setpoint Deadband