31
10.7 Output technical data
Relay(s)
Contacts 2 x single pole changeover relays (SPCO)
Voltage ratings (maximum) 250 Vac
Resistive load 3 amp @ 250 Vac
Inductive load 1 amp @ 250 Vac
ac motor load
¼ HP (2.9 amp) @ 250 Vac
1
/
10
HP (3 amp) @ 120 Vac
Pilot duty load C300 (2.5 amp) - control circuit/coils
Electrical life (operations) 3 x 10
5
or greater depending on load
Mechanical life (operations) 30 x 10
6
Infrared
Physical layer IrDA
Baud 38 400
Range 10 cm
Working angle 15°
Eye safety information
Exempt from EN 60825-12: 2007 Safety of laser products
- does not exceed the accessible emission limits (AEL) of
Class 1