IM-S51-07 CTLS Issue 1
SP7-10, SP7-11, SP7-12 and SP7-20, SP7-21, SP7-22 Parameterization
© Copyright 2022
SP7-10, SP7-11, SP7-12 and
SP7-20, SP7-21, SP7-22
Parameterization
IM-S51-07
CTLS Issue 1
Device firmware version 05: SP7-10 / SP7-20
Device firmware version 03: SP7-11 / SP7-12 / SP7-21 / SP7-22

Other manuals for Spirax Sarco SP7-11

Questions and Answers

  • B
    Bryan TaylorSep 15, 2025
    How to troubleshoot NO_COMM error on Spirax Sarco SP7-11 Valve Positioners?
    • D
      Dennis HansenSep 15, 2025
      If the Spirax Sarco Valve Positioners displays 'NO_COMM', check the bus address and status bit (128).
  • E
    Edward CollinsAug 25, 2025
    How to reset the travel counter on Spirax Sarco SP7-11 Valve Positioners (ALARM 7)?
    • E
      Elizabeth MooreAug 25, 2025
      To reset the travel counter on Spirax Sarco Valve Positioners after ALARM 7, use a connected PC with suitable software.
  • F
    Frederick HarrisAug 25, 2025
    What to do if Spirax Sarco SP7-11 show ALARM 5?
    • B
      Brian PayneAug 26, 2025
      If the Spirax Sarco Valve Positioners display ALARM 5, it means positioning has timed out because the settling time needed exceeds the configured stroke time. To resolve this, ensure that the actuator is not blocked, the supply air pressure is adequately high, and the specified time limit is higher than 1.5 times the longest stroke time of the actuator. If adaption cannot run uninterruptedly for an actuator, adaption should be switched on until the alarm does not occur anymore during controlling actions.
  • C
    Courtney StewartAug 26, 2025
    What to do if Spirax Sarco Valve Positioners display ERROR 10?
    • S
      Sergio AllenAug 27, 2025
      If your Spirax Sarco Valve Positioners are showing ERROR 10, it indicates that the supply voltage was interrupted for at least 20 ms. This error is displayed after resetting the device to indicate the reason for the reset. You should check the power source and the wiring to solve this problem.
  • M
    Maria HillSep 16, 2025
    What does ERROR 50 to 99 mean on Spirax Sarco SP7-11?
    • D
      David AdkinsSep 17, 2025
      If the Spirax Sarco Valve Positioners displays ERROR 50 to 99, and the error can be reproduced in the same position after resetting, the device must be returned for repair to the manufacturer. This indicates an internal error.
  • M
    mikayla94Sep 23, 2025
    What does NV_ERROR mean on Spirax Sarco Valve Positioners?
    • R
      Robert TapiaSep 23, 2025
      If the Spirax Sarco Valve Positioners displays 'NV_ERROR' it indicates a defective memory chip. Return the device for repair.
  • D
    debbiewilliamsSep 8, 2025
    Why does my Spirax Sarco Valve Positioners show CALC_ERR error?
    • S
      Shannon ClarkSep 8, 2025
      If the Spirax Sarco Valve Positioner displays 'CALC_ERR', this could be due to inconsistent data (e.g., a low value being higher than a high value) or incorrect configuration. You can correct the values or load the factory settings. Another cause could be that data cannot be saved locally because PROFIBUS saves data in the background. In this case, try again later.
  • F
    fcolonSep 9, 2025
    What to do if Spirax Sarco Valve Positioners show ERROR 10?
    • R
      Randy RossSep 9, 2025
      If your Spirax Sarco Valve Positioners show ERROR 10, it means the supply voltage was interrupted for at least 20 ms. To resolve this, check the power source and the wiring.
  • S
    seanwrightSep 2, 2025
    What does ALARM 4 mean on Spirax Sarco SP7-11 Valve Positioners?
    • J
      jessicaeatonSep 2, 2025
      ALARM 4 on Spirax Sarco Valve Positioners indicates that controlling is inactive because the device does not operate in control mode or the binary input is active. To resolve this, switch to control mode or switch off the binary input.
  • M
    margaret34Aug 31, 2025
    What causes ALARM 1 on Spirax Sarco Valve Positioners?
    • N
      Nathan MccoySep 1, 2025
      ALARM 1 on Spirax Sarco Valve Positioners is caused by leakage between the positioner and the actuator. To address this, check the piping.

Summary

4. Diagnosis and Error Messages

4.1 a Error Codes

Details of error codes, their causes, and troubleshooting.

4.1 b Specific SP7-11;12 and SP7-21;22 Error Messages

Specific error messages for SP7-11/12 and SP7-21/22 models.

4.2 Alarm Codes

List of alarm codes, their possible causes, and troubleshooting.

4.3 Message Codes

Codes and descriptions for various system messages.

4.4 Error Handling

Procedures for diagnosing and resolving positioner issues.

1. General Information

1.2 Warnings

Explanation of signal words DANGER, WARNING, CAUTION, and NOTE.

2. Operation

2.1 Safety Instructions

Safety precautions to be followed during operation.

3. Configuration

3.3 4.20 mA and 4-20 mA HART Parameter Descriptions (SP7-10 and SP7-20)

Detailed parameter descriptions for HART communication.

3.17 Profibus PA and Foundation Fieldbus Parameter Descriptions (SP7-11, SP7-12 and SP7-21, SP7-22)

Parameter mapping for Profibus PA and Foundation Fieldbus devices.

Spirax Sarco SP7-11 Specifications

General IconGeneral
Input Signal4-20 mA
Output Pressure0 to 100% of supply pressure
Supply Pressure20-100 psi (1.4-7.0 bar)
Enclosure RatingIP66 (NEMA 4X)
Ambient Temperature-40 to 85°C (-40 to 185°F)
MountingDirect mounting to actuator
MaterialsAluminum
TypeElectropneumatic positioner
ActionDirect or Reverse