IM-S51-07 CTLS Issue 1
SP7-10, SP7-11, SP7-12 and SP7-20, SP7-21, SP7-22 Parameterization
© Copyright 2022
SP7-10, SP7-11, SP7-12 and
SP7-20, SP7-21, SP7-22
Parameterization
IM-S51-07
CTLS Issue 1
Device firmware version 05: SP7-10 / SP7-20
Device firmware version 03: SP7-11 / SP7-12 / SP7-21 / SP7-22

Other manuals for Spirax Sarco SP7-11

Questions and Answers

  • J
    Jason WarrenSep 3, 2025
    What should I do if Spirax Sarco Valve Positioners display ERROR 50 to 99?
    • B
      Brian FuentesSep 3, 2025
      If your Spirax Sarco Valve Positioners display an error within the range of ERROR 50 to 99, it indicates an internal error. If the error can be reproduced and occurs in the same position after resetting, the device must be returned for repair to the manufacturer.
  • S
    seanwrightSep 2, 2025
    What does ALARM 4 mean on Spirax Sarco SP7-11 Valve Positioners?
    • J
      jessicaeatonSep 2, 2025
      ALARM 4 on Spirax Sarco Valve Positioners indicates that controlling is inactive because the device does not operate in control mode or the binary input is active. To resolve this, switch to control mode or switch off the binary input.
  • L
    lacey47Sep 1, 2025
    What to do if Spirax Sarco Valve Positioners show ERROR 20?
    • R
      Robert HuffmanSep 1, 2025
      If your Spirax Sarco Valve Positioners display ERROR 20, it indicates that there is no access possible to the data in the EEPROM. If resetting the device doesn't restore access, load the factory settings. If the error persists, the device must be returned for repair to the manufacturer.
  • M
    margaret34Aug 31, 2025
    What causes ALARM 1 on Spirax Sarco Valve Positioners?
    • N
      Nathan MccoySep 1, 2025
      ALARM 1 on Spirax Sarco Valve Positioners is caused by leakage between the positioner and the actuator. To address this, check the piping.
  • C
    christhomasAug 31, 2025
    What to do if Spirax Sarco SP7-11 display ALARM 3?
    • D
      David JohnsonAug 31, 2025
      If the Spirax Sarco Valve Positioners are showing ALARM 3, it means there is an alarm from the zero monitor, indicating that the zero position has shifted by more than 4%. To solve this, correct the mounting.
  • D
    Diana EatonAug 30, 2025
    What to do if Spirax Sarco Valve Positioners display ERROR 12?
    • S
      stronghelenAug 30, 2025
      If your Spirax Sarco Valve Positioners are displaying ERROR 12, it indicates that the position is outside the measuring range, possibly due to a malfunction in the position sensor. Check the mounting to resolve this issue.
  • A
    Angelica GloverAug 29, 2025
    How to fix ERROR 13 on Spirax Sarco Valve Positioners?
    • C
      christine89Aug 29, 2025
      ERROR 13 on Spirax Sarco Valve Positioners indicates an invalid input current, which occurs when the setpoint signal is overridden. To resolve this, check the power source and the wiring.
  • L
    Laura RodriguezAug 28, 2025
    What to do if Spirax Sarco Valve Positioners display ERROR 11?
    • K
      Kyle CastilloAug 28, 2025
      If the Spirax Sarco Valve Positioners are showing ERROR 11, it means the supply voltage has fallen below the minimum voltage. To solve this, check the power source and the wiring.
  • J
    Jessica Terrell DDSAug 27, 2025
    Why is my Spirax Sarco SP7-11 Valve Positioners showing ALARM 2?
    • A
      Angel GriffinAug 27, 2025
      Your Spirax Sarco Valve Positioners are showing ALARM 2 because the setpoint current is outside the permissible range, specifically less than 3.8 mA or greater than 20.5 mA. To fix this, check the power source.
  • C
    Courtney StewartAug 26, 2025
    What to do if Spirax Sarco Valve Positioners display ERROR 10?
    • S
      Sergio AllenAug 27, 2025
      If your Spirax Sarco Valve Positioners are showing ERROR 10, it indicates that the supply voltage was interrupted for at least 20 ms. This error is displayed after resetting the device to indicate the reason for the reset. You should check the power source and the wiring to solve this problem.

Summary

4. Diagnosis and Error Messages

4.1 a Error Codes

Details of error codes, their causes, and troubleshooting.

4.1 b Specific SP7-11;12 and SP7-21;22 Error Messages

Specific error messages for SP7-11/12 and SP7-21/22 models.

4.2 Alarm Codes

List of alarm codes, their possible causes, and troubleshooting.

4.3 Message Codes

Codes and descriptions for various system messages.

4.4 Error Handling

Procedures for diagnosing and resolving positioner issues.

1. General Information

1.2 Warnings

Explanation of signal words DANGER, WARNING, CAUTION, and NOTE.

2. Operation

2.1 Safety Instructions

Safety precautions to be followed during operation.

3. Configuration

3.3 4.20 mA and 4-20 mA HART Parameter Descriptions (SP7-10 and SP7-20)

Detailed parameter descriptions for HART communication.

3.17 Profibus PA and Foundation Fieldbus Parameter Descriptions (SP7-11, SP7-12 and SP7-21, SP7-22)

Parameter mapping for Profibus PA and Foundation Fieldbus devices.

Spirax Sarco SP7-11 Specifications

General IconGeneral
Input Signal4-20 mA
Output Pressure0 to 100% of supply pressure
Supply Pressure20-100 psi (1.4-7.0 bar)
Enclosure RatingIP66 (NEMA 4X)
Ambient Temperature-40 to 85°C (-40 to 185°F)
MountingDirect mounting to actuator
MaterialsAluminum
TypeElectropneumatic positioner
ActionDirect or Reverse