ASP 116 EVOLUTION INSTALLATION MANUAL
Sprinte SAS. All rights reserved , including translations.
40
Increase value if the targeted speed is not maintained ( ->15% for async.mot., ->10% for sync.mot)
Choose « NO ». Do not change
Brake settings on start-up
Set the brake opening time
Choose 0,3s for asynchronous motor
Choose 1s for synchronous motor.
For an open-loop asynchronous motor only:
Set the brake opening frequency.
Decrease value if a shock is felt on start-up.
Increase value in case of rollback on start-up (0,1Hz to 0,5Hz max)
Choose « 0,0 A » for Asynch. Motor, « -0,1A » for Synch. Motor.
Do not change
REJECTOR FILTER
NO
LOOP GAIN
10%
FREQ. INVERTER
BRAKE
BRAKE OPEN.TIME
1,00 s
BRAKE OPEN. FCY
0,1 Hz
BRAKE OPEN. I FW
-0,1 A
BRAKE
STARTUP ADJUST.
FREQ. INVERTER
SPEED LOOP
FREQ. INVERTER
BRAKE
ENTER
ENTER
BACK
-
-
-
-
-
BACK