Increase value if the targeted speed is not maintained ( ->15% for async.mot., ->10% for sync.mot)
Choose « NO ». Do not change
Brake settings on start-up
Set the brake opening time
Choose 0,3s for asynchronous motor
Choose 1s for synchronous motor.
For an open-loop asynchronous motor only:
Set the brake opening frequency.
Decrease value if a shock is felt on start-up.
Increase value in case of rollback on start-up (0,1Hz to 0,5Hz max)
Choose « 0,0 A » for Asynch. Motor, « -0,1A » for Synch. Motor.
Do not change