ASP 116 EVOLUTION INSTALLATION MANUAL
Sprinte SAS. All rights reserved , including translations.
58
5. Return to normal operation after exiting from pit inspection mode (EN81-20 §5.12.1.5.2.2.c )
Once pit inspection mode is over, an electrical reset system is required outside of the shaft
by EN81-20 standard , in order to ensure that the technician got out from the well.
The car doors are closing.
Unlock the landing doors and get out of the shaft
Once you’re out of the shaft , lock the landing doors
Once the landing doors are locked, you have 15 s to maintain the
landing call button for 5s (the button will beep to confirm).
3 x 5s
+
If all conditons of are not fulfilled, then the procedure gets back to
Otherwise
The return to normal operation has been properly done.
END
IN USE P 0
AVAILABLE
STEP 3
STEP 4
NOW LOCK THE
LANDING DOORS
FAIRE 3 AP EN 5S
POUR MODE NORMAL
VERR.PORTES
STEP 4
STEP 2
STEP 1
CLOSING DOORS
STEP 2
NOW UNLOCK THE
LANDING DOORS