SST-PFB-SLC User’s Guide
74
8.4 FDL Diagnostic Counters
The scanner maintains several diagnostic counters for FDL operation.
The scanner increments diagLay2MsgOk whenever it sends an FDL message
and receives the appropriate acknowledge or response data.
The scanner increments errLay2MsgNotOk whenever it sends a FDL
message and doesn’t receive an appropriate acknowledge or response data.
The scanner increments diagLay2SapOk when it processes an FDL SAP
request with no errors.
The scanner increments errLay2SapNotOk when there is an error receiving a
SAP request.
Name Location Description
diagLay2MsgOk 4116 FDL messages sent OK
errLay2MsgNotOk 4117L FDL message errors
diagLay2SapOk 4118 FDL SAP requests processed OK
errLay2SapNotOk 4119L FDL SAP errors