EasyManua.ls Logo

STG-BEIKIRCH TRZ Basic 4A - Function; Special Features

Default Icon
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
09/24999842
21
For smoke heat extraction and daily ventilation for 24 V DC linear drives and chain motors
Please keep these operating instructions for future reference and maintenance. Subject to technical modications. Diagram is not binding.
SHE control panel TRZ Basic 4A/UP
SHE control panel TRZ Basic 4A/UP
Function
Smoke extraction system preferably for electromechanical openings in
stairways. Opening of the smoke vent aps in case of re. Closing of the
smoke vent aps via closed-function.
Opening and closing for daily ventilation. Smoke vent aps* as dome lights,
folding skylights or windows with 24 V DC linear drives or chain motors.
* (hereafter referred to only as “windows”).
Special features
• function “daily ventilation”
• 1 SHE group and 1 ventilation group
• 24 V power supply, emergency power batteries and charging unit, parallel
operation, 72 hours of functioning guaranteed in case of power failure
• line monitoring of alarm circuits (autom. detectors and SHE man. call points)
• line monitoring of the connected drives
• adjustable extraction limit
• adjustable automatic ventilation, closing after 10 min.
• optical malfunction alarm
• separately fused power input 230 V AC / 50 Hz
• all outputs protected against shortcircuit
• temperature controlled battery charged voltage
• sheet steel housing for ush mounting
• ush mounting option with facing frame hinged door, lockable
• conforms to current state-of-the-arts standards
• processor controlled
• extension capabilities due to optional available plug-in modules
• TÜV type tested
TRZ Basic 4A/UP
Stiftleiste für
Erweiterungen
Pin ledge for
extensions
RWA-Reset
SHE Reset
Control board
Steuerplatine
Steckbrücken /
J1 Lüftungstaster “Sonderfunktion”
J2 Lüftungszeitautomatik
Jumper
J1 Vent switch “special function”
J2 Automatic control ventilation time
Betrieb OK
RWA Auf
Störung
Operating ok
SHE open
Malfunction
OK
!
TRZ Basic 4A/UP
Anzeige / Display
Jumper
J1 Vent switch, “special
function”, J2 Automatic
control ventilation time
Pin ledge
for
extensions
Display
Operating OK
SHE Open
Malfunction
Control board
SHE Reset