36 09/24999842
Technical datas
Mechanical properties
Dimensions: see page 34
Weight: approx. 16 kg with battery, approx. 10 kg without battery
Circuit connections and operation
Connections: see technical documentation
Terminal connections: see technical documentation
Suitable for SHE: yes
Suitable for ventilation: yes
Ventilation function in the event of
mains failure: no, ventilation blocked
Safety functions in the event of
mains failure: yes, automatic closure of the windows, ventilation blocked, while SHE continues to
be active
Maintenance
Battery replacement: every 4 years and in the event of battery malfunction
Maintenance counter: nonexistent
Adjustable functions
Stroke limitation: ON/OFF (only at ventilation operation)
Stop with key-operated vent switch: ON/OFF
Installation and ambient conditions
Rated temperature: 20 °C
Ambient temperature range: +5 °C to 40 °C
Installation condition: only for dry rooms
Function retention: Drives: 72 hours
Suitable for external mounting: no
IP protection system: IP 30 in accordance with DIN EN 60529
Authorisations and certications
CE compliant: in accordance with EMV directive 2004/108/EG and the low voltage directive
2006/95/EG
Class of protection: Class I in accordance with DIN 61140 (DE 0140-1)
Type tested: TÜV, Registration-No. 44 780 10 384797
Material
Housing: sheet steel
Housing door: swivelling (front door), lockable
Colour: RAL 9003 white
Optional accessories: AP-frame for surface mounting, sheet steel, white (RAL 9010), 336 x 348 x 91 mm
Halogen-free: yes
Silicon-free: yes
RoHS compliant: yes