INsTALLATIoN
Installation
www.stiebel-eltron.com  LWZ130 | 39
ENGLISH
The installation room must have an adequate condensate drain
with siphon.
Minimum clearances
≥20
≥10
≥200
≥400 ≥400
D0000068464
≥300
M8
D0000075157
The appliance must be accessible from below for changing filters
and maintenance purposes. Mount a cover (600 x 1200mm) be-
neath the appliance or design the suspended ceiling in such a way
that it is removable under the appliance.
9.3 Transport
!
Material losses
If possible, transport the appliance to the installation lo-
cation in its original packaging.
If the appliance is transported without packing and with-
out using a pallet, its outer casing may be damaged.
Make sure that no objects drill through the outer enve-
lope of the appliance.
!
Material losses
Never use the air connections as handles for carrying
the appliance.
10. Installation
WARNING Electrocution
Do not install the appliance if it is damaged and there is
a risk that live components could be touched.
Check the appliance for external damage.
!
Material losses
Make sure that there are no sharp objects at the in-
stallation location that could drill through the outer
envelope of the appliance.
10.1 Mounting the appliance
!
Material losses
Check whether the ceiling can bear the weight of the
appliance.
!
Material losses
Always install the appliance horizontally so that any
condensate arising can flow into the condensate
drain. The filter cassettes are located at the bottom
of the appliance.
Note
Install the appliance before mounting the ceiling panels
of the suspended ceiling.
Note
When positioning the appliance, ensure there is
sufficient space to install the supply and extract air
ducts (see chapter "Preparations/ Specification/
Installation site/ Minimum clearances").
Drill holes in the ceiling for mounting the appliance with
threaded pins or double ended screws.
Lift the appliance until the threaded pins are located in the
retainers on the sides of the appliance.
Screw a rubber buffer, washer and two nuts onto each
threaded pin.
Align the height with the first nut.
Secure the first nut with the second nut.
Level the appliance horizontally by turning the nuts to en-
sure that condensate can drain correctly. Use a spirit level to
check whether the appliance is level horizontally.
326794-41212-9444_LWZ_130_de_en.indb 39 09.05.2019 12:06:02

Table of Contents