INsTALLATIoN
Specication
www.stiebel-eltron.com  LWZ130 | 51
ENGLISH
17.4 Data table
LWZ 130 LWZ 130 Enthalpie
237805 237806
Sound emissions
Sound power level with standard ventilation and 50Pa external dB(A) 33 33
Sound power level (EN 12102) dB(A) 33 33
Application limits
Application range, outdoor air (temperature) °C -15-40 -15-40
Application range, extract air (temperature) °C 15-35 15-35
Energy data
Energy efficiency class A A
Electrical data
Rated voltage V 230 230
Phases 1/N/PE 1/N/PE
Frequency Hz 50 50
Power consumption incl. preheating coil A 5 5
Power consumption excl. preheating coil A 0.46 0.46
Max. power consumption W 87.9 71
Power consumption incl. preheating coil W 1150 1150
Power consumption excl. preheating coil W 105 105
Max. mains impedance Zmax Ω 0.32 0.32
Versions
Filter class ePM10 ≥ 50 % (M5) | ISO Coarse > 60 % (G4) ePM10 ≥ 50 % (M5) | ISO Coarse > 60 % (G4)
IP rating IP20 IP20
Dimensions
Height mm 248 248
Width mm 520 520
Depth mm 1113 1113
Weights
Weight kg 18 18
Connections
Air connector diameter mm 125 125
Condensate connection mm 16.5 16.5
Values
Heat recovery level up to % 87 87
Air flow rate m³/h 50-180 50-180
Min. ambient conditions, installation room (temperature) °C 2 2
Max. ambient conditions, installation room (temperature) °C 35 35
Storage and transport temperature °C 50 50
Available external pressure at max. air flow rate Pa 160 160
Heat recovery level % 87 87
Further details
LWZ 130 LWZ 130 Enthalpie
237805 237806
Maximum altitude for installation m 2000 2000
326794-41212-9444_LWZ_130_de_en.indb 51 09.05.2019 12:06:12