www.stiebel-eltron.com WPF | WPF cool | 39
INSTALLATION
Commissioning
Settings / DHW / electric reheating Setting range Standard System value
DUAL MODE TEMP DHW -40 to 40°C -20°C
LOWER APP LIMIT DHW OFF / -39.5 to 40°C -20°C
Settings / cooling / standard setting Setting range Standard System value
COOLING ON / OFF OFF
COOLING MODE PASSIVE / ACTIVE
Settings / cooling / active cooling / AREA COOLING Setting range Standard System value
SET FLOW TEMPERATURE 7 to 25°C 15°C
FLOW TEMP HYSTERESIS 1 to 5 K 5K
SET ROOM TEMPERATURE 20 to 30 °C 25°C
DYNAMIC 1 to 10 10
Settings / cooling / active cooling / fan cooling Setting range Standard System value
SET FLOW TEMPERATURE 7 to 25°C 15°C
FLOW TEMP HYSTERESIS 1 to 5 K 5K
SET ROOM TEMPERATURE 20 to 30 °C 25°C
DYNAMIC 1 to 10 10
Settings / cooling / passive cooling / AREA COOLING Setting range Standard System value
SET FLOW TEMPERATURE 7 to 25°C 15°C
FLOW TEMP HYSTERESIS 1 to 5 K 5K
SET ROOM TEMPERATURE 20 to 30 °C 25°C
Settings / cooling / passive cooling / fan cooling Setting range Standard System value
SET FLOW TEMPERATURE 7 to 25°C 15°C
FLOW TEMP HYSTERESIS 1 to 5 K 5K
SET ROOM TEMPERATURE 20 to 30 °C 25°C
Commissioning Setting range Standard System value
ENTER CODE 0000 to 9999 1000
LANGUAGE English
Source Setting range Standard System value
SOURCE TEMPERATURE MIN OFF / -10 to 10°C -9°C
BRINE PUMP RATING 20 to 100% 100 %
SOURCE MEDIUM Ethylene glycol
Heating Setting range Standard System value
HP SENSOR MAX 38 to 46 bar 40
CNTRL DYNAMIC 1 to 30 10
HEATING CIRCT PUMP RATING 20 to 100% 100 %
DHW Setting range Standard System value
DHW CIRCUIT PUMP RATING 20 to 100% 100 %
Compressor Setting range Standard System value
IDLE TIME 1 to 120 minutes 20 minutes
SINGLE PHASE OPERATION ON / OFF OFF
QUICK START ON / OFF OFF
EMERGENCY OPR ON / OFF OFF
HEAT PUMP RESET ON / OFF OFF
FAULT LIST RESET ON / OFF OFF
SYSTEM RESET ON / OFF OFF