COMMISSIONING
Menu
32 | WPM www.stiebel-eltron.com
Menu: COMMISSIONING
MINIMUM TEMPERATURE
Example for output X4.10
Here you can set the minimum temperature that must be present
at differential sensor1.1 for the pump to start, once the start
differential has been reached.
Note
Differential sensor1.1 must be installed at the heat
source (e.g. the water chamber of the stove).
MAXIMUM TEMPERATURE
Example for output X4.10
Here you can set the maximum temperature that must be present
at differential sensor1.2.
If the temperature at differential sensor1.2 is higher than the
maximum temperature, output X4.10 is switched off.
Note
Differential sensor1.2 must be installed at the heat store
(e.g.buffer cylinder).
STOP DELAY
Example for output X4.10
This parameter specifies a run-on time for the pump (output
X4.10).
THERMOSTAT FUNCTION 1/2
With the WPE heat pump extension, two thermostat functions
working independently of one another can be set up, each con-
trolling one output (X4.10 and X4.11). Output X4.10 is controlled
via thermostatic sensor1 (X3.9). Output X 4.11 is controlled via
thermostatic sensor2 (X 3.11).
THERMOSTAT FUNCTION 1/2
Set the parameter to ON or OFF.
SET TEMPERATURE
Example for output X4.10
Here you can set the temperature above which the output (X4.10)
switches on.
HYSTERESIS
Example for output X4.10
The value set here specifies the temperature difference from the
set temperature at which the output (X4.10) switches off.
COMMISSIONING
SOURCE
MIN SOURCE TEMPERATURE
SOURCE MEDIUM
ETHYLENE GLYCOL
WATER
GROUNDWATER MODULE
MAX. SOURCE EXTRACTION RATE
CHARGING PUMP CONTROL
STANDBY
TYPE OF CONTROL
MINIMUM PUMP RATE
AVERAGE PUMP RATE
MAXIMUM PUMP RATE
ADJUSTABLE PUMP RATE
SET VALUES
PUMP RATE
HEATING
TYPE OF CONTROL
MINIMUM PUMP RATE
AVERAGE PUMP RATE
MAXIMUM PUMP RATE
ADJUSTABLE PUMP RATE
SPREAD CONTROL
SET VALUES
PUMP RATE
SPREAD
DHW
TYPE OF CONTROL
MINIMUM PUMP RATE
AVERAGE PUMP RATE
MAXIMUM PUMP RATE
ADJUSTABLE PUMP RATE
SPREAD CONTROL
SET VALUES
PUMP RATE
SPREAD
COOLING
TYPE OF CONTROL
MINIMUM PUMP RATE
AVERAGE PUMP RATE
MAXIMUM PUMP RATE
ADJUSTABLE PUMP RATE
SPREAD CONTROL
SET VALUES
PUMP RATE
SPREAD
DEFROST
TYPE OF CONTROL
MINIMUM PUMP RATE
AVERAGE PUMP RATE
MAXIMUM PUMP RATE
ADJUSTABLE PUMP RATE
SPREAD CONTROL
SET VALUES
PUMP RATE
SPREAD
STANDARD SETTING