COMMISSIONING
Menu
40 | WPM www.stiebel-eltron.com
Menu: COMMISSIONING
ON
As soon as a FATAL ERROR occurs in heat pump types with internal
electric reheating and the heat pump fails, the operating mode
automatically switches over into emergency mode.
Every heat pump in a cascade must suffer a fatal error before
the program switch automatically switches over to emergency
operation.
There's one exception: Automatic emergency operation will also
be triggered if only the preselected heat pump for DHW fails.
In heat pump types with an external heat source, the second heat
source must be set to ON for central heating or DHW heating; only
then can it change over to emergency operation when a fatal
error occurs.
For heat pumps with a second heat source, the second heat source
takes over heating operation and DHW heating.
OFF
As soon as faults occur in heat pump types with internal electric
reheating and the heat pump fails, the second heat source for
central heating takes over frost protection. Heating operation and
DHW heating are not carried out.
RESET
 HEAT PUMP
If a fault occurs the heat pump can be reset. Setting it to ON clears
the fault that has occurred. The compressor starts again. The fault
remains stored in the message list.
 NOTIFICATION LIST
The entire message list is deleted.
 SYSTEM
A system reset will reset the heat pump manager to delivered
condition (factory settings).
 FET
With this reset, you reset all installed FET remote controls. The
heating circuits can be reassigned.
 WPE
A system reset will reset the heat pump extension to delivered
condition (factory settings).
SENSOR CALIBRATION
If the sensors do not measure the temperature correctly, you can
correct the measured temperature by +/-5K in this menu.
 ACTUAL FLOW TEMPERATURE WP
Correct the measured temperature by +/-5K.
 ACTUAL FLOW TEMPERATURE NHZ
Correct the measured temperature by +/-5K.
 ACTUAL RETURN TEMPERATURE WP
Correct the measured temperature by +/-5K.
UPDATE