COMMISSIONING
Menu
38 | WPM www.stiebel-eltron.com
Menu: COMMISSIONING
 HEATING
In this menu item you can set the temperatures to be targeted by
the heat pump manager if the external voltage signal for heating
mode is present.
Note
If a voltage of 2 to 9V is present, the preset temperatures
are interpolated accordingly.
 PRESET TEMPERATURE 1V
Set here the temperature that should be targeted by the heat
pump manager if a voltage of 1V is present at inputX1.15.
 PRESET TEMPERATURE 10V
Set here the temperature that should be targeted by the heat
pump manager if a voltage of 10V is present at inputX 1.15.
 COOLING
In this menu item you can set the temperatures to be targeted by
the heat pump manager if the external voltage signal for cooling
mode is present.
Note
If a voltage of 2 to 9V is present, the preset temperatures
are interpolated accordingly.
 PRESET TEMPERATURE 1V
Set here the temperature that should be targeted by the heat
pump manager if a voltage of 1V is present at inputX1.15.
 PRESET TEMPERATURE 10V
Set here the temperature that should be targeted by the heat
pump manager if a voltage of 10V is present at inputX 1.15.
 OUTPUT X1.16/X1.17
In this menu item you can adjust the settings for the pump con-
nected to the output.
 PWM 0%...100%
10
A
100
100
0 7 12 15 95 PWM %
max
min
n/¹/min
D0000076328
A Setting range
The pump speed is controlled in proportion to the PWM input
signal. The pump stops if there is a cable break.
Set this parameter to ON if you connect a pump for solar
thermal energy.
Observe the operating instructions of the pump
manufacturer.
 PWM 100%...0%
max
n/¹/min
min
10
0 5
A
100
10085 88 90 PWM %
D0000076327
A Setting range
The pump speed is controlled in inverse proportion to the PWM
input signal. If there is a cable break, the pump runs at maximum
speed.
Set this parameter to ON if you connect a heating circuit
pump.
Observe the operating instructions of the pump
manufacturer.
 0-10 V
Set this parameter to ON if you use a pump that is controlled
by a 0-10V voltage signal.
 OUTPUT
Select here the pump that is connected to the output.
You have the following options:
- Buffer charging pump (BUFFER CHARGING PUMP 1 / 2)
- Heating circuit pump (HK PUMP 1 / 2 / 3)
- DHW charging pump (DHW CHARGING PUMP)
- Source pump (SOURCE PUMP)
- CHARGING PUMP CONTROL HEATING
- CHARGING PUMP CONTROL DHW
 OUTPUT
In this menu item, you can assign a signal strength for pulse width
modulation to the connected pump. The signal is used to specify
the flow rate, output or set speed.
Please also note the information on flow rate (see the operat-
ing instructions for the pump and the chapter “Specification/
Data table” in the operating and installation instructions for
the heat pump).