8 | Connection STOBER
90
04/2021 | ID 442537.08
8.4.15 X15: Safety technology – Safe outputs,
supply for X50 (SE6 option)
The SE6 safety module adds the expanded safety functions to the SD6 drive controller using terminals X14 and X15.
Information
If you would like to use the expanded safety functionality over terminals, be sure to read the SE6 manual; see the chapter
Detailed information [}161].
ATTENTION!
Loss of safety!
Overvoltages > 40V
DC
in the coupling between the safety module and safety controller can lead to loss of safety. Exposing
the digital 1-pole outputs of the safety module to an overvoltage of the safety controller can cause the deactivated outputs
to output a 1 signal. For the safety controller, use a power supply unit with overvoltage protection for the output voltage.
The output voltage must be limited to a maximum of 40V
DC
.
Technical data
Observe the technical data of the safety options at X14 and X15; see the chapter SE6 [}33].
Terminal Pin Designation Function
5 | 6 | 7 | 8
1 | 2 | 3 | 4
1 +24V 24 V
DC
supply for digital outputs (PELV); fuse
protection: max. 4AT; the supply voltage is also
needed if no safe outputs are used
2 O0 Safe digital output
3 O1 Safe digital output
4 U
2
Power supply voltage for external encoder
5 O2 Safe digital output
6 O3 Safe digital output
7 O4 Safe digital output
8 0V GND Reference potential for external encoder
Tab. 86: X15 connection description
Connecting wiring
For connecting wiring, observe the terminal specifications in the chapter DFMC 1.5 -ST-3.5 [}155].
Cable requirements
Feature All sizes
Max. cable length 30m
Tab. 87: Cable length [m]