StoneL publication 105431revC
7 PI 70 en Prism PI | 13
4.1 Sensor/switching modules
4.1.3 Expeditor, standard stroke (80S & 80W)
Specications
Position control (AO) 4-20 mA loop, 9-30 VDC (NAMUR NE 43 compliant)
Intermediate control range 20% - 80% of valve stroke
Intermediate control
accuracy
+/- 3 % of valve stroke
Maximum resistance load 425 ohms @ 24 VDC
Solenoid voltage 24VDC
Solenoid power 100 mA
Refresh rate 100 ms
LED states 4.0 - 7.1 mA = red LED / valve closed
7.2 - 16.8 mA = yellow LED / intermediate state
16.9 - 20 mA = green LED / valve open
Cycle life 500,000 cycles (full cycles with intermediate positioning,
cycle life may vary depending on intermediate toggling)
Wiring diagrams
Basic installation example
Teach
Valve Open/
Closed LEDs
Intermediate
Position
Y
Y
G G
Valve Open/
Closed LEDs
R
R
+
-
SEC SOL PRI SOL VDC IN CNTRL IN
-
-
+ +-
+
Description of operation
The Prism Expeditor is a valve monitoring and control package for linear
actuators that provides open/closed and intermediate positioning
functionality. Basic operation and intermediate control is accomplished
by 24VDC and a 4-20mA output signal from a control system.
Basic operation
The Prism Expeditor module is powered through the VDCIN terminals
and 24VDC must be present in order to calibrate the unit. The
CNTRLIN signal is also required for basic operation of the unit.
To stroke the valve fully closed position, apply a 4mA signal. To stroke
the valve fully open, apply a 20mA signal.
Intermediate position control
Intermediate positioning is accomplished by varying the 4-20mA
signal between 7.2mA and 16.8mA.
Note
Applying an out of range 4-20mA signal (<3.4mA or >21.1mA)
will drive valve to the 0% position and unlock the Wireless Link
control override functionality. Wireless functionality allows remote
monitoring, position control and TEACH capabilities. See page22
for Wireless Link user guide.
WARNING
Do not apply external power to the primary or secondary
solenoid terminals. This will cause permanent damage to the unit.
Calibration
The VDCIN terminals must be connected to a 24VDC power source
and unit connected to supply air.
1. Actuate the valve to the 0% position, red LED will be lit.
2. Press and hold the TEACH button for 2 seconds. The valve will
cycle open and closed one or more times while determining the
valve operating characteristics. The red, green, and yellow LEDs will
ash intermittently during these cycles.
3. Calibration will nish with the valve at the commanded position
and the appropriate LED will be lit.
24 VDC
4-20 mA
OUT
24 VDC
Prism Expeditor
Computer control system
PRI SOL -
PRI SOL +
VDC IN -
VDC IN +
CNTRL IN -
CNTRL IN +
SEC SOL -
SEC SOL +
Caution: Read all instructions prior to performing this
procedure.
WARNING
Valve/actuator will automatically stroke while performing this
procedure. Ensure hands are clear from the trigger assembly.
Specications for Wireless Link
Communication Bluetooth® technology; single mode
(not compatible with Bluetooth® Classic)
Frequency band 2.402-2.480 Ghz
Transmit power 4dBm or ~2.5 milliwatts
Data rate 1 Mbit/second; eective information transmit rate
~10 Kbits/second
Range Up to 100 meters (330 feet) in free space. Range is
reduced by obstructions between handheld device and
Wireless Link VCT. Line of site is not necessary.
Registrations FCC, IC, CE
CE compliance Exceeds industrial compliance standards
VCT identication VCTs in range will be displayed in order of signal
strength
VCT link One device accessed at a time between client (hand-
held device) and server (VCT). Each server accessed by
one client at a time
Application StoneL Wireless Link available from the App store
Hand-helds Compatible with iPhone® and iPad® with iOS 8 or later