7 PI 70 en24 | Prism PI
StoneL publication 105431revC
Image 5
A
B
C
5.5 More information screen
To see additional information about a specic valve, swipe right or use
the arrows at the top of the device detail screen.
1. At the top of the more Information screen (Image5), the unit
model number, serial number, and date code are displayed
(ItemA). These are preset from the factory and cannot be changed.
2. There are two customizable text boxes titled “Valve/Actuator
Description” and “Additional Information” where up to 160
characters can be added for user notes, such as maintenance or
service records (ItemB).
Website and instruction manual
The direct links to StoneL’s website and the unit installation,
Maintenance and Operating Instructions located on the bottom
buttons of the More Information screen require an internet
connection to access (ItemC).
Image 4c - Expeditor detail
O
P
Q
5.4 Device detail screen continued
Changing the device tag on an expeditor unit
1. To change the tag, edit the existing tag in the associated text eld
(ItemO). The tag can be up to sixteen characters long.
Calibrating the valve assembly
1. Actuate the valve to the CLOSED position.
2. Select teach (Item P). A warning screen will appear indicating this
action could disrupt the process. Select cancel or continue.
3. Select continue. The valve will cycle open and closed one or more
times while determining the valve operating characteristics.
4. Calibration will nish with the valve in the commanded position
and the appropriate light illuminated (Item Q).
5. You can verify intermediate control functionality using the
diagnostics screen (Image 6c).