24 V 6.1.0 Quick guide
Level
Nr
VarioString parameter description
Factory value
Expert
14071
Operating mode (AUX 1)
Automatic
Expert
14072
Combination of the events for the auxiliary contact (AUX 1)
Any (Function OR)
Expert
14073
Contact activated in night mode (AUX 1)
Expert
14074
Activated in night mode (AUX 1)
No
Expert
14075
Delay of activation after entering night mode (AUX 1)
1 min
Expert
14076
Activation time for the auxiliary relay in night mode (AUX 1)
1 min
Expert
14206
Contact active with a fixed time schedule (AUX 1)
Expert
14207
Contact activated with fixed time schedule (AUX 1)
No
Expert
14208
Start hour (AUX 1)
07:00 hh:mm
Expert
14209
End hour (AUX 1)
20:00 hh:mm
Expert
14077
Contact active on event (AUX 1)
Expert
14188
VarioString is ON (AUX 1)
No
Expert
14078
VarioString is OFF (AUX 1)
No
Expert
14214
Remote entry (AUX 1)
No
Expert
14079
Battery undervoltage (AUX 1)
No
Expert
14216
Battery undervoltage
40 Vdc
Expert
14080
Battery overvoltage (AUX 1)
No
Expert
14081
Earth fault (AUX 1)
No
Expert
14082
PV error (48h without charge) (AUX 1)
No
Expert
14083
Overtemperature (AUX 1)
No
Expert
14084
Bulk charge phase (AUX 1)
No
Expert
14085
Absorption phase (AUX 1)
No
Expert
14086
Equalization phase (AUX 1)
No
Expert
14087
Floating (AUX 1)
No
Expert
14088
Reduced floating (AUX 1)
No
Expert
14089
Periodic absorption (AUX 1)
No
Expert
14090
Contact active according to battery voltage (AUX 1)
Expert
14091
Battery voltage 1 activate (AUX 1)
No
Expert
14092
Battery voltage 1 (AUX 1)
46.8 Vdc
Expert
14093
Delay 1 (AUX 1)
1 min
Expert
14094
Battery voltage 2 activate (AUX 1)
No
Expert
14095
Battery voltage 2 (AUX 1)
47.8 Vdc
Expert
14096
Delay 2 (AUX 1)
10 min
Expert
14097
Battery voltage 3 activate (AUX 1)
No
Expert
14098
Battery voltage 3 (AUX 1)
48.5 Vdc
Expert
14099
Delay 3 (AUX 1)
60 min
Expert
14100
Battery voltage to deactivate (AUX 1)
54 Vdc
Expert
14101
Delay to deactivate (AUX 1)
60 min
Expert
14102
Deactivate if battery in floating phase (AUX 1)
No
Expert
14103
Contact active according to battery temperature (AUX 1)
With BSP or BTS
Expert
14104
Contact activated with the temperature of battery (AUX 1)
No
Expert
14105
Contact activated over (AUX 1)
3 °C
Expert
14106
Contact deactivated below (AUX 1)
5 °C
Expert
14107
Only activated if the battery is not in bulk phase (AUX 1)
No
Expert
14108
Contact active according to SOC (AUX 1) Only with BSP
Expert
14109
Contact activated with the SOC 1 of battery (AUX 1)
No
Expert
14110
Contact activated below SOC 1 (AUX 1)
50 % SOC
Expert
14111
Delay 1 (AUX 1)
12 hours