Studer Innotec SA
Quick guide RCC-02/-03
Quick guide V 6.1.0 41
(203): External alarm leaves
The communicating battery has deactivated a
warning (problem solved) via the Xcom-CAN. The
features that were temporarily deactivated are
now automatically reactivated thanks to the
Xcom-CAN's communication with the battery.
Error (204): External stop arrives
The communicating battery has activated an
alarm (problem occurred) via the Xcom-CAN.
Some features of the installation may be
temporarily disabled. Depending on the severity
of the problem, the battery may disconnect from
the installation (opening the internal relays of the
battery). The BMS can continue to operate and
still communicate depending on the battery used
(depending on the manufacturer).
ATTENTION, in this case it is possible that the
devices shut off completely as they no longer
receive power from the battery (0V on the battery
terminals +BAT et -BAT).
(205): External stop leaves
The communicating battery has deactivated an
alarm (problem solved) via the Xcom-CAN. If the
battery has been disconnected (opening of the
internal battery relays), the battery must be
restarted (please follow the battery activation
procedure provided by the manufacturer).
Halted (206): Board hardware
incompatibility
This message appears when the hardware
versions of the PCB and Control boards are not
compatible. The message could be due to
hardware problems, or problems reading the
version (e.g. the device has condensation).
(207): AUX1 relay activation
The conditions are met for the activation of AUX1
relay. The cause of the activation can be seen on
the RCC-02/03.
(208): AUX1 relay deactivation
The conditions required for the activation of relay
AUX1 are not all present, and therefore AUX1 is
deactivated. The cause of the deactivation can
be seen on the RCC-02/03.
(209): AUX2 relay activation
The conditions are met for the activation of AUX2
relay. The cause of the activation can be seen on
the RCC-02/03.
(210): AUX2 relay deactivation
The conditions required for the activation of relay
AUX2 are not all present, and therefore AUX2 is
deactivated. The cause of the deactivation can
be seen on the RCC-02/03.
(211): Command entry deactivated
XT: The remote entry is deactivated and therefore
the corresponding programming will not be
performed. This is referring to the effective
deactivation and therefore will depend on the
setting of {1545}, not if the remote entry is
physically open or shut.
VT: When parameter {10317} is used, a message is
sent in the event of deactivation of the remote entry.
VS: When parameter {14205} is used, a message is
sent in the event of deactivation of the remote entry.