14.10.5 Maximum current of the AC source (Input limit) {1107}
Adjust this configuration in the event of
connection to a limited power source, for
example, a generator of moderate power output
or a dock or camping connection. The
adjustment of this value limits the instantaneous
power consumed from the source in charger
mode. The power available is attributed by first
priority to consumers and then to battery
charging. If the consumption level changes, the
battery charge current is automatically adjusted.
A. Power available and used to recharge the
batteries
B. Maximum AC source current (adjusted to 10
A here)
C. Consumer current
D. Power supplied by the inverter (Smart-Boost
function)
If the consumption level is higher than the controlled level, the maximum source
current will be exceeded, except when the Smart-Boost function is activated.
It’s possible to access faster to this function, please refer to the page 16
14.10.6 Adaptation of the input current {1471}
With this sub-menu you can adjust the value of the AC current taken from the source, according to
various external parameters:
14.10.6.1 Using a secondary value for the maximum current of the AC source
{1566}
If this parameter is activated the value set for the maximum current of the source is inverted with the
value programmed by the parameter below, when the command entry is activated.
14.10.6.2 Second maximum current of the AC source {1567}
Value used instead of the main value when the command entry is activated.
Use this function if you connect regularly two different souces like a generator and a shore
power. By using this function you can change from one input limit to another by means
of an information contact on the command entry. Without having to program the
maximum value at each change of source.
14.10.6.3 Decrease of the max. current of the source with input voltage {1554}
This parameter activates the function”Decrease of the source max. current with the input
voltage”{1527} but only when the command entry is activated too.
Usefull in cases where a second source must be stabilized by means of this function
but not the first source, like for instance the public grid and a generator (joint use with
{1566} and {1567}).