ENGLISH ALARM THERMOSTAT HIGH TEMP
• Internal temperature probe: when this alarm is active, no device is disabled.
• Condenser fan thermic: when this alarm is active, the compressor is switched off.
• Condenser pressure: when this alarm is active, the compressor is switched off.
• Danfoss compressor communication error
When this alarm is active, the compressor is switched off and the data point Modbus 40301 for the communication
with the Danfoss compressor is forced to 0.
• Ambient temperature invalid: when this alarm is active, the compressor is switched off.
• Peripherals error: when this alarm is active, the compressor is switched off.
• EEV IN failure: when this alarm is active, the compressor is switched off.
• Discharge temperature invalid: when this alarm is active, the compressor is switched off.
• Alarm active: when this alarm is active, the compressor is switched off.
7.26. Custom 26
• Control: Same control of standard application but with freecooling mode disabled
• Alarm: Power failure. If this alarm occurs, the freecooling mode will be enabled.
7. 2 7. Custom 27
Same functionality of customs 23. On the fourth line of the information screen is not shown the name of the customer.
7.28. Custom 28
Control
Same control of standard application
Warning
Fc stop by wind
The parameter involved is:
• I107 SELECT RELAY FC STOP BY WIND: pre-set = NO CONN.
The signal of warning is A3 digital input. If this warning occurs, the freecooling will be switched off. The reset is automatic.
It’s possible to connect the warning to a relay and/or to associate it to “common warning” or “common alarm” relay by
parameter I107.
In the following table the “warning description” is shown as it will appear on the LCD during warning condition or in the
alarm history menu.
ENGLISH WARNING FC STOP BY WIND