Alarm
Fc stop by fire
The parameter involved is:
I108 SELECT RELAY FC STOP BY FIRE: pre-set = CA
The signal of alarm is A1 digital input. If this alarm occurs, the freecooling will be switched off. The reset is manual.
It’s possible to connect the alarm to a relay and/or to associate it to “common warning” or “common alarm” relay by
parameters I108.
In the following table the “alarm description” is shown as it will appear on the LCD during alarm condition or in the alarm
history menu.
ENGLISH WARNING FC STOP BY FIRE
7.29. Custom 29
Control
Same control of standard application
Alarm
Evaporator fan 1 broken
The parameter involved is:
I109 SELECT RELAY EVAPORATOR FAN 1 BROKEN: pre-set = CA
The signal of alarm is A7 digital input. The alarm will be active with a delay of 1 second. If this alarm occurs, the
machine goes in emergency mode. The reset is manual at the fourth attempt within 4 hours (I.e. the reset is automatic
for 3 attempts during 4 hours. If it occurs more than 3 times, the reset will be manual).
It’s possible to connect the alarm to a relay and/or to associate it to “common warning” or “common alarm” relay by
parameters I109.
In the following table the “alarm description” is shown as it will appear on the LCD during alarm condition or in the
alarm history menu.
ENGLISH WARNING EVAP. FAN 1 BROKEN
Evaporator fan 2 broken
The parameter involved is:
I110 SELECT RELAY EVAPORATOR FAN 2 BROKEN: pre-set = CA
The signal of alarm is A12 digital input. The alarm will be active with a delay of 1 second. If this alarm occurs, the
machine goes in emergency mode. The reset is manual at the fourth attempt within 4 hours (I.e. the reset is automatic
for 3 attempts during 4 hours. If it occurs more than 3 times, the reset will be manual).
It’s possible to connect the alarm to a relay and/or to associate it to “common warning” or “common alarm” relay by
parameters I110.
In the following table the “alarm description” is shown as it will appear on the LCD during alarm condition or in the
alarm history menu.
ENGLISH WARNING EVAP. FAN 2 BROKEN