Window 3.a (OPERATE->value)
It’s possible to set:
(S001) Cooling set point
(S002) Second cooling set point
(S003) Heating set point
(S004) Second heater set point
(S005) Humidity set point
(S006) Cooling band
(S007) Heating band
(S008) Humidity band
(S009) Alarm limit low temperature
(S010) Hysteresis of low temperature alarm
(S011) Alarm limit high temperature
(S012) Hysteresis of high temperature alarm
(S013) Alarm limit max temperature
(S014) Hysteresis of max temperature alarm
(S015) Alarm limit low humidity
(S016) Alarm limit high humidity
(S017) Alarm delay (humidity - temperature)
(S018) Intrusion-vibration alarm delay
(S019) Limit supply temp in freecooling mode
(S020) Language selection
(S027) Password user
Window 3.b (OPERATE->machine)
It’s possible:
Switching on/off the machine
Resetting the alarms