Config
Components/heater
Electric heater
The PIN assignment of the electric heater is described in chapter “3.1.1 PIN assignment
- I/O controller” on page 7.
You add an electric heater to the configuration by setting the “ACTIVE” parameter to 1.
You deactivate the heater with “0”. ➊
You define the heater type in the following line (2 step: heater with on/off control, linear:
heater with proportional regulation). ➋
You determine the digital output ➌ for the heater using the “D-OUT” parameter.
The proportionally-regulated electric heater is controlled via the pulse width modulation
and receives the control signal via a determined PWM output. A digital output does not
need to be determined for the proportionally-regulated electric heater.
Alarm parameters:
Digital input ➍
Common alarm actuation ➎
Alarm priority ➏
PWW heater
You add a PWW valve to the configuration by setting the “ACTIVE” parameter to 1. You
deactivate the valve with “0”. ➊
You define the valve type in the following line (2 step: solenoid valve with on/off control,
linear: 3-way valve with proportional regulation). ➋
You determine the digital output for the solenoid valve using the “D-OUT”
parameter. ➌
You determine the analog output of the proportional signal for the PWW valve of the
PWW heater with the “A-OUT” parameter. ➍
Electric heater type:
Type 1: On/Off control
Type 2: Proportional regulation
Valve type:
Type 1: On/Off control
Type 2: Proportional regulation