Electrical Requirements
Installation must comply with all applicable electrical codes.
Locate the electrical supply within the shaded area shown
in the illustration below. A separate circuit servicing only
this appliance is required. A ground fault circuit interrupter
(GFCI) is not recommended and may cause interruption of
operation.
ELECTRICAL REQUIREMENTS
Electrical Supply 115 VAC, 60 Hz
Service 15 amp dedicated circuit
Receptacle 3-prong grounding-type
Site Preparation
75
1
/2" (1918)
FROM FLOOR
7"
(178)
E
6"
(152)
RIGHT SIDE
OF OPENING
Electrical supply location
CAUTION
The outlet must be checked by a qualified electrician
to be sure it is wired with the correct polarity. Verify
the outlet is properly grounded.
WARNING
If the supply cord is damaged, it must be replaced by
the manufacturer, its service agent or similarly quali-
fied persons in order to avoid a hazard.
WARNING
Do not use an extension cord, two-prong adapter, or
remove the power cord ground prong.
WARNING
Do not locate multiple portable socket-outlets or
portable power supplies at the rear of the appliance.