Section 6
CONTROLLER COMMUNICATION
PROTOCOL
32
Table 6.3 Parameter Descriptions
NetTag
II S WS Description Digits Units
3 RW RW RW Language n list
4 RW Units of measure n list
4 RW RW Temp units of measure n list
5 RW RW RW Unload Pressure nnn psi
6 RW RW RW Load Pressure delta nn psi
8 RW RW RW Unload Time nn min
9 RW RW RW Wye-Delta time nn sec
10 RW RW RW Drain Interval Time nn min
11 RW RW RW Drain Time nn sec
12 RW RW RW Restart time nn sec
18 RW RW Sequence com number nn
19 RW RW eConnect ID nn
20 RW RW RW Seq number of machines nn
21 RW RW RW Sequence method n list
22 RW RW RW Sequence hours nnnnnn hour
23 RW RW RW Sequence lowest pressure nnn psi
24 RW RW RW Sequence recover time nn sec
25 RW RW R Machine max capacity nnnnn cfm
26 RW RW RW Seq Rotate time nnn hour
30 RW RW Modulate n y/n
31 RW RW Pressure units n list
32 RW RW VSD setpoint nnn psi
40 RW T1 calibrate n
41 RW T2 calibrate n
42 RW T3 calibrate n
43 RW T4 calibrate n
44 RW T5 calibrate n
45 RW T6 calibrate n
45 RW RW Pressure calibrate password nnn
46 RW RW RW P1 calibrate n
47 RW RW RW P2 calibrate n
48 RW RW RW P3 calibrate n
49 RW RW P4 calibrate n
50 RW RW dP1 calibrate n
51 RW P3 maximum n
54 RW Maintenance warning nnnn hour
55 RW Maintenance filter nnnnn hour
56 RW Maintenance separator nnnnn hour
57 RW Maintenance air filter nnnnn hour
58 RW Maintenance oil nnnnn hour
59 RW Maintenance oil analysys nnnnn hour
70 RW RW Parameter protection n y/n
71 RW RW Shutdown on warning n y/n
80 R R Load cycles (read only) nnnnnn
81 R R Number of starts (read only) nnnnnn
98 R R Run hours (read only) nnnnnn hour
99 R R Load hours (read only) nnnnnn hour
R = Read Only, RW = Read-Write