What causes Battery Group DC V-Diff too Large on Sungrow EMS200 Controller?
- KKeith PageSep 8, 2025
If the Sungrow Controller displays a Battery Group DC V-Diff too Large error, and you have multiple BCPs or the system in which battery DC sides are directly connected in parallel, and "Battery Direct Connect Voltage Value" is greater than the set value, check whether the parameter is set to an appropriate value. Also, check whether the system voltage difference between battery racks whose DC sides are connected in parallel is relatively large.