85
figure 7-18 Reactive Power Regulation
table 7-9 Reactive Power Regulation
Parameter
Definition/Setting
Description
Range
Reactive power genera-
tion at night
Switch for enabling/disabling
Q at night function.
Enable/Disable
Reactive power ratio at
night
Reactive power ratio set for
the Q at night function.
-100%~0%/
0%~100%
Reactive power setting
persistence
Switch for enabling/disabling
the power-off function during
reactive power.
Enable/Disable
Reactive power regula-
tion mode
Off/PF/Qt/Q(P)/Q(U)
Reactive power
regulation
Switch for enabling/disabling
reactive response function.
Enable/Disable
Reactive power regula-
tion time
Ends time of reactive
response.
0.1s~600.0s
Q(P)Curve Select corresponding curve
according to local regulations
Curve A/Curve B/Curve C*
QP_P1 Output power at P1 on the Q
(P) mode curve (in
percentage)
0.0%~100.0%
QP_P2 Output power at P2 on the Q
(P) mode curve (in
percentage)
20.0%~100.0%
User Manual 7 iSolarCloud App

Table of Contents

Other manuals for Sungrow SG30CX