86
Parameter
Definition/Setting
Description
Range
QP_P3 Output power at P3 on the Q
(P) mode curve (in
percentage)
20.0%~100.0%
QP_K1 Power factor at P1 on the Q(P)
mode curve
Curve A/Curve
C:0.800~1.000
Curve B: [-0.600~0.600]*Ac-
tive Overload Rate/1000
QP_K2 Power factor at P2 on the Q(P)
mode curve
Curve A/Curve C:
0.800~1.000
Curve B: [-0.600~0.600]*Ac-
tive Overload Rate/1000
QP_K3 Power factor at P3 on the Q(P)
mode curve
Curve A/Curve C:
0.800~1.000
Curve B: [-0.600~0.600]*Ac-
tive Overload Rate/1000
QP_EnterVoltage Voltage percentage for Q(P)
function activation
100.0%~110.0%
QP_ExitVoltage Voltage percentage for Q(P)
function deactivation
90.0%~100.0%
QP_EXitPower Power percentage for Q(P)
function deactivation
1.0%-20.0%
QP_EnableMode Unconditional activation/deac-
tivation of Q(P) function
Yes/No
Q(U)Curve Select the corresponding
curve according to local
regulations
Curve A/Curve B/Curve C*
QU_V1 Pre-set grid voltage U1 that is
reactive according to the grid
voltage
80.0%~100.0%
QU_Q1 Pre-set proportion of reactive
power according to the grid
voltage U1
[-60.0%-0]* Overload Rate/
1000
7 iSolarCloud App User Manual

Table of Contents

Other manuals for Sungrow SG30CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG30CX and is the answer not in the manual?

Sungrow SG30CX Specifications

General IconGeneral
BrandSungrow
ModelSG30CX
CategoryInverter
LanguageEnglish

Related product manuals