EasyManua.ls Logo

SystemAir SAVE VTR 300/B - Heat Exchanger and Fan Servicing

SystemAir SAVE VTR 300/B
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.2.2PerformFactoryreset
Howtoperformafactoryresetifnecessary:
1.Entertheservicemenubyselectingtheservice
symbolinthedisplayandpressENTER.
2.Gotopasswordandenterthepassword,
default1111
UsetheSELECTIONknobforeachdigitand
ENTERwiththeENTERbuttonaftereachsetdigit
andchooseNOforthesystemnotbelocked.
Password
PasswordXXXX
LockedYES/NO
3.GotoFunctionsandselectFactoryReset
Functions
Factoryreset
4.TurntheSELECTIONknobsoYESisshown
andpressENTER.
Factoryreset
Reallyreset?YES/NO
5.ACCEPTEDisshowninthedisplaywindow
ACCEPTED
6.TheStartupWizardstartsafterapproximately
10seconds
6.3Systemcurves
Asystemrequiresdifferentpressuresatdifferentairows,whichcanberepresentedbyasystemcurve.
Theintersectionbetweenthesystemlineandthefancurve,istheunit'sworkingpoint.Itisshowingthe
airowthesystemisgoingtohave.Everychangeinthepressureoftheventilationsystem,willgive
risetoanewsystemcurve.
TheK-factorisaconstantthatisthesamethroughoutoneandthesamesystemcurve.IftheK-factorand
thesystempressureisknown,theairowcanbecalculated.Iftherealpressuredropinthesystemis
largerorsmallerthancalculated,theworkingpointandtheairowwillbedifferentthanexpected.
SAVEVTR300/BInstallationandService
208348
13
SystemairAB

Other manuals for SystemAir SAVE VTR 300/B

Related product manuals