6.4Fanspeedsettings
Thefanspeedcanbesetbyeitherl/s,m
3
/horapercentage.
•IfAirflowischosenintheservicemenu,thesettingswillbeinl/sandsystemcurvesareselected.
•IfSpeedischosenintheservicemenu,thesettingswillbeinpercentage.Systemcurvesarenot
selectable.
Thefanspeedmaybeadjustedinfoursteps;off,low,nominalandhigh.Thesesettingscontroltheoutput
signalstothesupply-andextractfans.Thefactorysettingoneachspeedstepsare:
•Off:0l/s
•Low:49l/sor25%.
•Nom:82l/sor50%(atapproximately80Pa).
•High:100l/sor100%.
Theselevelsarepossibletochangeintheservicelevel.Seeservicemenuoverview(chapter8.5)under
functions.
Note:
Itisnotrecommendedtoactivatemanualfanstop(setfantoOFF)instandardhouseholds.
Ifmanualfanstopisactivated,theunitshouldbeprovidedwithdampersinexhaustandfreshairductsto
avoidcolddraughtandriskofcondensationwhentheunithasbeenstopped.
ThefancanbesettoOFFbyactivatingmanualfanstop.Seeservicemenuoverview(chapter8.5)
underfunctions.