6.6ProgrammingtheWeekschedule
Settheweekscheduleaccordingtobelowprocedure:
1.Gototheservicemenubyusingthe
SELECTIONknob.
2.Entertheservicelevelbytypingthepassword,
default1111.UsetheSELECTIONknobforeach
digitandconrmwiththeCONFIRMbuttonafter
eachsetdigitandchoose"NO"forthesystemnot
belocked.
Password
PasswordXXXX
LockedYES/NO
3.Goto:Weekprogram
Service
Weekprogram
4.ChooseWeekprogramagain.
Weekprogram
Fanspeed
5.Setweekdayandtimeyouwanttheunitto
beinONlevel.Twoperiodsperdaycanbe
programmed.Therestofthetimetheunitwillbein
OFFlevel.
Weekprogram
Day:MON
Per1:07:0016:00
Per2:00:0000:00
6.Gobacktothepreviousdialogueframewiththe
BACKbuttonandgodowntoFanspeed.
Weekprogram
Fanspeed
7.Setwhichfanspeedthefanissupposedtobe
runningintheONlevel,choosebetweenLow,
NomorHigh.
Setwhichfanspeedthefanissupposedtobe
runningintheOFFlevel,choosebetweenOFF,
Low,NomorHigh.
Note:
Ifanelectricalre-heaterbatteryisinstalledand
activeandtheunitisshutdownfromthecontrol
panel,forexamplebychoosingOFF.Whenthe
unitisinOFFlevelintheweekprogram,thefans
willcontinuetorunfor3minutes,topreventthe
heaterfromtriggeringtheoverheatprotection
sensor,beforetheystop.
Fanspeed
Onlevel:low/nom/high
Offlevel:off/low/nom/high
8.StepbackwiththeBACKbuttonuntilyoureach
themainmenudisplay
SAVEVTR300/BInstallationandService