MFC Kit Instructions 5.0 PQconnect Option
46
PCB under temperature
clear threshold*
STATUS_T_AMBIENT_UT_DELAY
642
Input
DEFAULT: = 6
seconds.
Range 1 to 3600
seconds
Status detection delay time
in seconds.
PCB under temperature
delay threshold*
STATUS_T_AMBIENT_OT_ONSET
645
Input
DEFAULT: = 750 =
75C
Range 10C to 85C
Status detection measure in
degrees Celsius.
PCB over temperature
onset threshold*
STATUS_T_AMBIENT_OT_CLEAR
646
Input
DEFAULT: = 700 =
70C
Range 10C to 80C
PCB over temperature clear
threshold*
STATUS_T_AMBIENT_OT_DELAY
647
Input
DEFAULT: = 6
seconds.
Range 1 to 3600
seconds
Status detection delay time
in seconds.
PCB over temperature
delay threshold*
STATUS_PHASE_LOSS_ONSET
650
Input
DEFAULT: = 60 = 60
%
Range 1 to 100
Filter output voltage phase
loss onset threshold*
STATUS_PHASE_LOSS_CLEAR
651
Input
DEFAULT: = 65 =
65%
Range 1 to 100
Filter output voltage phase
loss clear threshold*
STATUS_PHASE_LOSS_DELAY
652
Input
DEFAULT: = 6
seconds.
Range 1 to 3600
seconds
Status detection delay time
in seconds.
Filter output voltage phase
loss delay threshold*
STATUS_CPU_ERROR_DELAY
655
Input
DEFAULT: = 6
seconds.
Range 1 to 3600
seconds
Status detection delay time
in seconds.
PCB processor CPU error
delay*
STATUS_HIGH_THD_WARNING_ONS
ET
660
Input
DEFAULT: = 12 = 12
%
Range 1 to 100
Filter output voltage high
THD onset threshold*
STATUS_HIGH_THD_WARNING_CLEA
R
661
Input
DEFAULT: = 11 =
11%
Range 1 to 100
Filter output voltage high
THD clear threshold*
STATUS_HIGH_THD_WARNING_DELA
Y
662
Input
Status detection delay
time in seconds.
DEFAULT: = 6
seconds.
Range 1 to 3600
seconds
Filter output voltage high
THD delay threshold*
STATUS_MIN_DETECTION_VOLTAGE
670
Input
DEFAULT: = 5 = 5%
of rated voltage
Range 1 to 100
Minimum voltage to enable
status detection*
FUND_MIN_TRACKING_VOLTAGE
680
Input
DEAULT: = 5 = 5% of
rated voltage
Range 1 to 100
Minimum voltage to enable
output voltage tracking. If
the filter output voltage is
below this threshold the
waveform data will be
zeroed out and the
metering data will report a
value 65535 (or 0xFFFF