EasyManua.ls Logo

TDK-Lambda LS Series - Page 14

TDK-Lambda LS Series
23 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
All specifications are subject to change without notice.
LS150 Specifications
LS
150
MODEL
ITEMS/UNITS
LS150-3.3 LS150-5 LS150-12 LS150-15 LS150-24 LS150-36 LS150-48
Input
Voltage Range (*2)
V
AC88 - 132 / AC176 - 264 Input Selectable or DC248 - 373
(Withstand AC300 Surge for 5 seconds)
Frequency (*2)
Hz 47-63
Efficiency(230VAC)(typ) (*1)
% 75 79 83 85 86 87
Current(115/230VAC)(typ) (*1)
A 3.5 / 2.0
Inrush Current(typ) (*3)
A 40A at 230VAC, Ta=25°C (Cold Start)
Leakage Current (*10)
mA < 1mA at 230VAC, 60Hz
Output
Nominal Voltage
VDC 3.3 5 12 15 24 36
48
Maximum Current A 30 26 12.5 10 6.5 4.3
3.3
Maximum Power W 99 130 150 156 154.8
158.4
Maximum Line Regulation (*5)(*6)
mV 20 48 60 96 144
192
Maximum Load Regulation (*5)(*7)
mV 40 96 120 192 288
384
Temperature Coefficient Less than 0.02%/°C
Maximum Ripple & Noise (*1)(*4)
mVp-p
80 120 150
200
Hold-up Time(115/230VAC)(typ) (*1)
ms 25 / 30
Voltage Adjustable Range
VDC 3 - 3.6 4.75 - 5.5 10.8 - 13.2 13.5 - 16.5 22 - 27.2 32 - 40
42 - 54
Function
Over Current Protection (*8) A > 110% rated output power
Over Voltage Protection (*9)
VDC 3.8 - 4.45 5.75 - 6.75 13.8 - 16.2
17.25 - 20.25
27.6 - 32.4 41.4 - 48.6
55.2 - 64.8
Series Operation Possible
Environment
Operating Temperature (*11) °C - 25 - + 70 (Refer to Output Derating Curve)
Storage Temperature
°C - 40 - +85
Operating Humidity
%
RH
20 - 90 (No dewdrop)
Storage Humidity
%
RH
10 - 95 (No dewdrop)
Vibration
At no operating, 10 - 55Hz (sweep for 1min)
19.6m/s² Constant, X, Y, Z 1hour each.
Shock(In Package)
Less than 196.1m/s²
Cooling
Convection cooling
Isolation
Withstand Voltage
Input - Output : 3.0kVAC (20mA), Input - FG : 1.5kVAC (20mA)
Output - FG : 500VAC (100mA) for 1min.
Isolation Resistance
Input - FG, Input - Output and Output - FG: More than 100M
Ω
(500VDC) at 25°C and 70%RH
Standards
Safety Standards Approved by UL60950-1, EN60950-1, IEC60950-1
PFHC(230VAC) (*1)
Built to meet IEC61000-3-2, -3
EMI
Built to meet EN55011/EN55022-B, FCC-B
Immunity
Built to meet EN61000-4-2 (Level 2,3), -3 (Level 3), -4 (Level 3),
-5 (Level 4), -6 (Level 3), -8 (Level 4), -11
Mechanical
Weight(typ) g 700
Size (W×H×D)
mm 199 x 98 x 38 (Refer to Outline Drawing)
(*1) At Maximum Output Power, nominal input voltage, Ta = 25°C.
(*2)
For cases where conformance to various safety specs (UL, CSA, EN) are required, to be described as 100 - 240VAC, 50 / 60Hz on name plate.
(*3)
Not applicable for the in-rush current to Noise Filter for less than 0.2mS.
(*4)
Ripple & noise are measured at 20MHz by using a 300mm twisted pair of load wires terminated with a 0.1uF film capacitor and a 47uF
electrolytic capacitor.
(*5)
Measure line & load regulation at output terminal M3.5 tapped point.
(*6)
88 - 132VAC or 176 - 264VAC, constant load.
(*7)
No load - Full load (Maximum power ), constant input voltage.
(*8)
Current limit with automatic recovery. Avoid to operate at overload or dead short for more than 30 seconds.
(*9)
OVP circuit will shutdown output, manual reset (Re-power on).
(*10)
Measured by each measuring method of UL and EN (at 60Hz), Ta=25°C.
(*11)
Refer to Output Derating Curve (PA579-01-02_) for details of output derating versus ambient temperature and mounting method.
(*12)
All parameters NOT specifically mentioned are measured at 115/230VAC input, rated load and Ta = 25°C.