7.
Run unit for 2 hours.
8. Stop unit and check oil sample with acid test kit. If the test kit shows there
is no acid in the system, you can proceed to reclaim the charge and
reassemble unit. If the acid test check fails change the suction line drier
and repeat the steps above.
9. Only after the system has past the acid test check can it be put together to
its proper running condition.