11
Group 00: Basic Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
00-19
Jog
Acceleration
Time
0.1~0600.0 - *1
00-20
Jog
Deceleration
Time
0.1~0600.0 - *1
00-21
Acceleration
time 3
0.1~6000.0 * *1
00-22
Deceleration
time 3
0.1~6000.0 * *1
00-23
Acceleration
time 4
0.1~6000.0 * *1
00-24
Deceleration
time 4
0.1~6000.0 * *1
00-25
Switch-Over
Frequency of
Acc/Dec Time
1 and Time 4
0.00~599.00 0.0
00-26
Emergency
Stop Time
0.1~6000.0 5.0
00-27
HD/ND Mode
Selection ***
0: HD (Heavy
Duty Mode)
0 *3
1: ND (Normal
Duty Mode)
00-28
Command
Characteristic
selection of
master
frequency
0: Positive
Characteristic
(0~10V/4~20mA
is corresponding
to 0~100%)
0
1: Negative
Characteristic
(0~10V/4~20mA
is corresponding
to 100~0%)
00-29
Zero-Speed
Operation
Selection
0: Operation
Based on
Frequency
Command
0
1: Stop
2: Operation
Based on the
Lowest
Frequency
3: Zero-Speed
Operation
00-30
00-31
Reserved
00-32
Application
Selection
Presets**
0: General
0
1: Reserved
2: Conveyor
3: Exhaust Fan
4: Reserved
5: Compressor
6: Hoist**
7: Crane**
8: Manual Pulse
Generator
(MPG)
(Note4)
Group 00: Basic Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
00-33
Modified
Parameters
(only for LCD
keypad)
0:Disable
0 *7
1:Enable
00-34
~
00-40
Reserved
00-41
User
parameter 0
Set 13-06 = 1,
start user
parameter. The
setting range is
01-00 ~22-31
(only for LCD
keypad)
00-41 *7
00-42
User
parameter 1
00-42 *7
00-43
User
parameter 2
00-43 *7
00-44
User
parameter 3
00-44 *7
00-45
User
parameter 4
00-45 *7
00-46
User
parameter 5
00-46 *7
00-47
User
parameter 6
00-47 *7
00-48
User
parameter 7
00-48 *7
00-49
User
parameter 8
00-49 *7
00-50
User
parameter 9
00-50 *7
00-51
User
parameter 10
00-51 *7
00-52
User
parameter 11
00-52 *7
00-53
User
parameter 12
00-53 *7
00-54
User
parameter 13
00-54 *7
00-55
User
parameter 14
00-55 *7
00-56
User
parameter 15
00-56 *7
00-57
SV High
Speed Mode
0: SV High
Speed Mode1
0
1: SV High
Speed Mode2
*: Refer to the attachment 1 in our instruction manual.
**: Before to set up 00-32 Application, it should do
initialized setting (parameter 13-08) first. When
setting 00-32, the I/O port function changed
automatically. To avoid accident, be sure to confirm
the I/O port signal of inverter and external terminal
control.
*** If parameter 00-27 is set to ND mode, group 02 motor
1 parameter will automatically adjust to more than 1
class of it.
If parameter 00-27 is set to HD mode, group 02 motor 1
parameter will automatically adjust to the same class
of it.
It is suggested that parameter 00-27 be set first
before motor performs auto-tuning because the

Other manuals for TECO A510s Series