4.4 Auto-tuning Error
When a fault occurs during auto-tuning of a
standard AC motor, the display will show the
“AtErr” fault and the motor stops. The fault
information is displayed in parameter 17-11.
Note: The fault contact output does not
energize with an auto-tuning fault. Refer to
Table 4.3, for fault information during tuning,
cause and corrective action.
Table 4.3 Auto-tuning fault and corrective
actions
Error Corrective action
01
Motor data input
error.
Check the motor tuning
data (17-00 to 17-09).
Check inverter capacity
02
Motor lead to
lead resistance
R1 tuning error.
Check the motor tuning
data (17-00 to 17-09).
Check motor connection.
Disconnect motor load.
Check inverter current
detection circuit and
DCCTs.
Check motor installation.
03
Motor leakage
inductance
tuning error.
04
Motor rotor
resistance R2
tuning error.
05
Motor mutual
inductance Lm
tuning error.
07
Deadtime
compensation
detection error
06
Motor encoder
error
Check motor rated
current.
Check PG card
grounding.
08
Motor
acceleration
error (Rotational
type auto-tuning
only).
Increase acceleration
time (00-14).
Disconnect motor load.
09
Other
Check the motor tuning
data (17-00 to 17-09).
Check motor connection.
4.5 PM motor Auto-tuning Error
When a fault occurs during auto-tuning of a PM
motor, the display will show the “IPErr” fault
and the motor stops. The fault information is
displayed in parameter 22-18.
Note: The fault contact output does not
energize with an auto-tuning fault. Refer to
Table 4.4, for fault information during tuning,
cause and corrective action.
Table 4.4 Auto-tuning fault and corrective
actions for PM motor
Error Corrective action
01
Magnetic pole
alignment tuning
failure (static).
Check the motor tuning
data (22-02).
Check inverter capacity
02
PG option
missing.
Install PG feedback
card.
03 Magnetic pole
alignment auto-
tuning abort
during rotational
auto-tune
Check for active
protection functions
preventing auto-tuning.
04
Timeout during
magnetic pole
alignment during
rotational auto-
tune.
Check motor.
Check motor wiring.
Check brake released.
05
Circuit tuning
time out.
Check for active
protection functions
preventing auto-tuning.
06
Encoder error
Check motor rated
current.
Check PG card
grounding.
07
Warning
Check the motor tuning
data (22-02).
Check motor
connection.
08
Motor current out
of range during
magnetic pole
alignment
(rotational auto-
tune).
Check PG card wiring
Check motor
connection.
09
Current out of
range during
circuit tuning.
Check the motor tuning
data (22-02).
Check inverter capacity
10
Magnetic pole
alignment and
circuit tuning
failed.
Retry magnetic pole
alignment and circuit
tuning.