2.2 General Wiring Diagram
Vcc 24V 12V 5V
R2K 750 100
Notes:
*1: Models 200V 1 ~ 25HP and 400V 1 ~ 40HP or lower ratings have a built-in braking transistor. To use this braking
transistor a braking resistor can be connected between B1 and B2.
*2: Use SW3 to select between Sink (NPN, with 24VG common) or Source (PNP, with +24V common) for multi-function
digital input terminals S1~S8.
*3: Use SW2 to switch between voltage (0~10V) and current (4~20mA) input for Multi-function analog input 2 (AI2).
Besides please also check parameter 04-00 for proper setting.
*4: Run Permissive input F1 and F2 is a normally closed input. This input should be closed to enable the inverter output.
To activate this input remove the jumper wire between F1 and F2.
*5: Models 200V 3HP and 400V 5HP and higher ratings include terminals -10V, S(+), S(-),R2A-R2C and PO-GND.
*6. 200V 2HP and 400V 3HP and lower ratings include terminal DO2.
*7: When using the open collector for pulse input, it doesn’t need resistance because of built-in pull-up resistance.
*8: AO2 default setting is 0~+10V.
*9 Both 200V class 50HP~150HP and 400V class 100HP~425HP have built-in DC reactors.
*10 It need turn on the switch for the terminal resistor RS485 in the last inverter when many inverters in parallel
connection. Please refer to Appendix A