6
2.3 Power Terminals
Terminal
200V: 1 ~ 25HP
400V: 1 ~ 40HP
575V: 1 ~ 10HP
690V: 15 ~ 40HP
200V: 30 ~ 150HP
400V: 50 ~ 425HP
690V: 50 ~ 270HP
R/L1
Input Power Supply (For single phase use terminals R/L1 and S/L2)
S/L2
T/L3
B1P
B1P: DC power supply
B1PB2: external braking resistor
-
B2
-: DC power supply or
connect braking module
-
U/T1
Inverter output
V/T2
W/T3
E Ground terminal
2.4 User Terminals (Control Circuit Terminals)
200V: 1 ~ 2 HP, 400V: 1 ~ 3HP
200V: 3 ~ 40 HP, 400V: 5 ~ 75HP, 575V:1~10HP, 690V: 15~75HP
R1A R1B R1C
R2A R2C RJ45
200V: 50 ~ 150 HP, 400V: 100 ~ 425HP, 690V: 100~270HP
R2A R2C R1A R1B R1C RJ45
Description of User Terminals
Type Terminal Terminal Function Signal Level / Information
Digital
input
signal
S1
2-wire forward/ stop (default) * 1
Signal Level 24 VDC
(photo isolated)
Maximum current: 8mA
Maximum voltage: 30 Vdc
Input impedance: 4.22k
S2
2-wire reversal/ stop (default) * 1
S3
Multi-speed/ position setting command 1 (default) * 1
S4
Multi-speed/ position setting command 2 (default) * 1
S5
Multi-speed/ position setting command 3 (default) * 1
S6
Fault reset (default) * 1
S7
JOG frequency command (default) * 1
S8
External B.B.(Base Block) stop (coast to stop)
(default) * 1
24V
Power
supply
24V
Digital signal SOURCE point (SW3 switched to
SOURCE )
±15%,
Max. output current: 250mA
(The sum of all loads
connected )
24VG
Common terminal of Digital signals
Common point of digital signal SINK ( SW3 switched
to SINK )