46
LED display Possible solutions
FU
fuse open
ï‚· Check IGBTs
ï‚· Check for short circuit at
inverter output.
ï‚· Replace inverter.
CF00
Operator
Communication
Error
ï‚· Disconnect the operator
and then reconnect.
ï‚· Replace the control board
CF01
Operator
Communication
Error 2
ï‚· Disconnect the operator
and then reconnect.
ï‚· Replace the control board
CTER
CT Failure
ï‚· Check current
transformer signal and
the voltage on the control
board.
CF20
Communication
Failure
ï‚· Check only use one kind
of communication type.
Protection
Failure
ï‚· Remove digital input
communication run
command
External
Overload
ï‚· Check external overload.
ï‚· Reset external overload
of digital input.
4.3 Warning / Self-diagnosis
Detection Function
When the inverter detects a warning, the
keypad displays a warning code (flash).
Note: The fault contact output does not
energize on a warning and the inverter
continues operation. When the warning is no
longer active the keypad will return to its
original state.
When the inverter detected a programming
error (for example two parameters contradict
each other of are set to an invalid setting), the
keypad displays a self-diagnostics code.
Note: The fault contact output does not
energize on a self-diagnostics error. While a
self-diagnostics code is active the inverter
does not accept a run command until the
programming error is corrected.
Note: When a warning or self- diagnostic error
is active the warning or error code will flash on
the keypad. When the RESET key is pressed,
the warning message (flash) disappears and
returns after 5 sec. If the warning or self-
diagnostic error still exists.
Refer to Table 4.2 for and overview, cause and
corrective action for inverter warnings and self-
diagnostic errors.
Table 4.2 warning / self-diagnosis and corrective
actions
LED display Corrective action
OV
(flash)
Over voltage
ï‚·
Increase deceleration
time
ï‚· Reduce input voltage to
comply with the input
voltage requirements or
install an AC line
reactor to lower the
input voltage.
ï‚· Remove the power
factor correction
capacitor.
ï‚· Use dynamic braking
unit.
ï‚· Replace braking
transistor or resistor.
ï‚· Adjust speed search
parameters.
UV
(flash)
under voltage
ï‚·
Check the input voltage.
ï‚· Check input wiring.
ï‚· Increase acceleration
time.
ï‚· Check power source
ï‚· Replace pre-charge
contactor
ï‚· Replace control board
or complete inverter.
OH1
Heatsink
overheat
ï‚· Install fan or AC to cool
surroundings.
ï‚· Replace cooling fan.
ï‚· Reduce carrier
frequency.
ï‚· Reduce load / Measure
output current