13
Group 02: IM Motor Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
02-00
No-Load
Current of
Motor1
0.01~600.00 -
02-01
Rated Current
of Motor1
Modes of V/F,
V/F+PG are
10%~200% of
inverter’s rated
current. Modes
of SLV, SV are
25%~200% of
inverter’s rated
current.
-
02-02 Reserved
02-03
Rated
Rotation
Speed of
Motor1
0~60000 -
02-04
Rated
Voltage of
Motor1
200V: 50.0~240.0
-
*8
400V: 100.0~480.0
-
575V: 150.0~670.0
-
690V: 200.0~804.0
-
02-05
Rated Power
of Motor1
0.01~600.00 -
02-06
Rated
Frequency of
Motor1
4.8~599.0
50.0/
60.0
*8
02-07
Poles of
Motor 1
2~16(Even) 4
02-08 Reserved
02-09
Excitation
Current of
Motor 1
15%~70% of
Motor Rated
Current
-
02-10
Core
Saturation
Coefficient 1
of Motor 1
1~100 -
02-11
Core
Saturation
Coefficient 2
of Motor 1
1~100 -
02-12
Core
Saturation
Coefficient 3
of Motor 1
80~300 -
02-13
Core loss of
Motor 1
0.0~15.0 -
02-14 Reserved
02-15
Resistance
between
Wires of
Motor 1
0.001~60.000 -
02-16
~
02-18
Reserved
02-19
No-Load
Voltage of
Motor 1
200V: 50~240 -
400V: 100~480 -
575V: 420~600 -
690V: 504~720 -
Group 02: IM Motor Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
02-20
No-Load
Current of
Motor 2
0.01~600.00 -
02-21
Rated Current
of Motor 2
10%~200% of
inverter’s rated
current
-
02-22
Rated
Rotation
Speed of
Motor 2
0~60000 -
02-23
Rated
Voltage of
Motor 2
200V: 50.0~240.0
-
*8
400V: 100.0~480.0
-
575V: 150.0~670.0
-
690V: 200.0~804.0
-
02-24
Rated Power
of Motor 2
0.01~600.00 -
02-25
Rated
Frequency of
Motor 2
4.8~599.0
50.0/
60.0
*8
02-26
Poles of
Motor 2
2~16 (Even) 4
02-27
~
02-31
Reserved
02-32
Resistance
between
Wires of
Motor 2
0.001~60.000 -
02-33
Proportion of
Motor 1
Leakage
Inductance
0.1~15.0 3.4
02-34
Motor 1 Slip
Frequency
0.10~20.00 1.00
02-35
~
02-36
Reserved
02-37
Motor
Mechanical
Loss
0.0~10.0 4.0
Group 03: External Digital Input and
Output Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
03-00
Multi-Function
Terminal
Function
Setting-S1
0: 2-Wire
Sequence
(ON: Forward
Run Command)
0
1: 2-Wire
Sequence (ON:
Reverse Run
Command)
2: Multi-
Speed/Position