EasyManua.ls Logo

TECO F510 series - Page 27

TECO F510 series
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
Group 08 Protection Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Level
08-45
PTC
Disconnectio
n Detection
0: Disable
0
Note3
1: Warning
2: Fault
08-46
Over-
temperature
Protection
Level
0~254°C 0
Note6
08-47
Over-
temperature
Reset Level
0~254°C 0
Note6
08-48
Fire Mode
Selection
0: Disable
1: Enable
0
Note6
08-49
Fire Mode
Digital Input
Type
0: Power Loss
Reset
1: Terminal
Removal Reset
0
Note6
08-50
Fire Mode
Digital
Terminal
Status
XXX0b: S6 A
contact
XXX1b: S6 B
contact
0000b
Note6
08-51
Fire Mode
Motor
Speed
Selection
0: Fire Mode
Operation
1: PID
Frequency
Command
2: AI2
Frequency
Command
0
Note6
08-52
Fire Mode
Motor
Speed
0.00~100.00 100.00
Note6
08-53
Fire Mode
PID
Detection
Level
0~100 0
Note6
08-54
Fire Mode
PID
Disconnecti
on Delay
0.0~10.0 1.0
Note6
08-55
Fire Mode
PID
Disconnecti
on
Selection
0: Current
Speed
1: Fire Mode
Speed (08-52)
2: Motor 1
Maximum
Frequency (01-
02)
1
Note6
08-56
Fire Mode
AI2
Detection
Level
0.0~100.0 80.0
Note6
08-57
Fire Mode
AI2
Disconnecti
on Delay
0.0~10.0 1.0
Note6
08-58
Fire Mode
AI2
Disconnecti
on Selection
0: Current
Speed
1: Fire Mode
Speed (08-52)
1
Note6
Group 08 Protection Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
2: Motor 1
Maximum
Frequency (01-
02)
08-59
Fire Mode
Motor
Direction
0: Forward
Direction
1: Reverse
Direction
0
Note6
08-60
Fire Mode
Password
00000~65534 0
Note6
Note: Models of inverter ratings for 2060 and
4100 above in IP20 enclosure do not have this
function.
Group 09: Communication Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
09-00
INV
Communica
tion Station
Address
1~31 1 *2
09-01
Communica
tion Mode
Selection
0: MODBUS
0
1: BACNET
2: METASYS
3: PUMP in
Parallel
Connection
4: PROFIBUS
09-02
Baud Rate
Setting
(bps)
0:1200
4
*2
*6
1:2400
2:4800
3:9600
4:19200
5:38400
09-03
Stop Bit
Selection
0:1 Stop Bit
0 *2
1: 2 Stop Bit
09-04
Parity
Selection
0: No Parity
0 *2 1: Even Bit
2: Odd Bit
09-05
Communica
tions Data
Bits
Selection
0: 8 bits data
0
Note1
1: 7 bits data
09-06
Communica
tion Error
Detection
Time
0.0~25.5 0.0
09-07
Fault Stop
Selection
0: Deceleration
to Stop Based
on Deceleration
Time 1 when
Communication
Fault Occurs.
3
1: Coast to
Stop when
Communication
Fault Occurs.
2: Deceleration

Other manuals for TECO F510 series

Related product manuals