25
Group 08 Protection Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Detection 1: Start to
Detect when
Reaching the
Set Frequency.
2: Start to
Detect when
the Operation
is Begun.
08-14
Selection of
Over-
Torque
Operation
0: Deceleration
to Stop when
Over-Torque is
Detected.
0
1: Display
Warning
when Over-
Torque is
Detected. Go
on Operation.
2: Coast to
Stop when
Over Torque
is Detected
08-15
Level of
Over-
Torque
Detection
0~300 150
08-16
Time of
Over-
Torque
Detection
0.0~10.0 0.1
08-17
Selection of
Low-Torque
Detection
0: Low-Torque
Detection is
Disabled.
0
1: Start to
Detect when
Reaching the
Set Frequency.
2: Start to
Detect when
the Operation
is Begun.
08-18
Selection of
Low-Torque
Operation
0: Deceleration
to Stop when
Low- Torque is
Detected.
0
1: Display
Warning when
Low- Torque is
Detected. Go
on Operation.
2: Coast to
Stop when
Low-Torque is
Detected
08-19
Level of
Low-Torque
Detection
0~300 30
08-20
Time of
Low-Torque
Detection
0.0~10.0 0.1
Group 08 Protection Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
08-21
Limit of Stall
Prevention
in Acc over
Base Speed
1~100 50
08-22
Stall
Prevention
Detection
Time in
Operation
2~100 100
08-23
Ground
Fault (GF)
Selection
0: Disable
0
1: Enable
08-24
Operation
Selection of
External
Fault
0: Deceleration
to Stop
0
1: Coast to
Stop
2: Continuous
Operation
08-25
Detection
selection of
External
Fault
0: Immediately
Detect when
the Power is
Supplied.
0
1: Start to
Detect during
Operation
08-26
~
08-29
Reserved
08-30
Selection of
Run
Permissive
Function
0: Deceleration
to Stop
0
1: Coast to
Stop
08-31
~
08-34
Reserved
08-35
Fault
Selection of
Motor
Overheat
0: Disable
0
1: Deceleration
to Stop
2: Coast to
Stop
08-36
Time
Coefficient
of PTC
Input Filter
0.00 ~ 5.00 2
08-37
Fan Control
Function
(Note)
0: Start at
Operation
0
1: Permanent
Start
2: Start at High
Temperature(N
ote)
08-38
Delay Time
of Fan Off
0~600 60
08-39
Delay Time
of Motor
Overheat
Protection
1~300 60
08-42
PTC Trip
Level
0.1~10.0 0.7
Note1
08-43 PTC Reset 0.1~10.0 0.3
Note1