Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Waking up
10-20
Delay Time
of PID
Waking up
0.0~255.5 0.0
10-21 Reserved
10-22
Start Level
of PID
Enable
0.00~400.00 0.00
Note2
10-23 PID Limit 0.00~100.0 100.0 *1
10-24
PID Output
Gain
0.0~25.0 1.0
10-25
PID
Reversal
Output
Selection
0: Do not Allow
Reversal
Output
0
1: Allow
Reversal
Output
10-26
PID Target
A
cceleration/
Deceleration
Time
0.0~25.5 0.0
10-27
PID
Feedback
Display Bias
0~9999 0
10-28 Reserved
10-29
PID Sleep
Selection
0: Disable
1 1: Enable
2: Set by DI
10-30
Upper Limit
of PID
Target
0.0 ~ 100.0 100.0
10-31
Lower Limit
of PID
Target
0.0 ~ 100.0 0.0
10-32
PID
Switching
Function
0: PID1
0
1: PID2
2: Set by DI
3: Switch to
PID2 when
RTC Timer
Enables
10-33
PID
Maximum
Feedback
Value
1~10000 999
10-34
PID Decimal
Width
0~4 1
10-35 PID Unit
0: %
0 *6
1: FPM
2: CFM
3: PSI
4: GPH
5: GPM
6: IN
7: FT
8: /s
9: /m
10: /h
11: °F
12: inW
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
13: HP
14: m/s
15: MPM
16: CMM
17: W
18: KW
19: m
20: °C
21: RPM
22: Bar
23: Pa
24: KPa
Note4
10-36
PID2
Proportional
Gain (P)
0.00~10.00 3.00 *1
10-37
PID2
Integral
Time (I)
0.0~100.0 0.50 *1
10-38
PID2
Differential
Time (D)
0.00~10.00 0.00 *1
10-39
PID Output
Frequency
Setting during
disconnection
00.00~400.00 30.00 *6
10-40
Compensatio
n Frequency
Selection of
PID Sleep
0: Disable
0
Note1
1: Enable
10-41
~
10-43
Reserved
10-44
Precharge
Frequency
0.0~120.0 0
Note3
10-45
Precharge
Time
0~250 0
Note3
10-46
Precharge
Target Level
0~10000 0
Note3
10-47
Proportional
Gain 3(P)
0.00~10.00
3.00
Note6
10-48
Integral
Time 3(I)
0.00~100.00
0.50
Note6
10-49
Differential
Time 3(D)
0.00~10.00
0.00
Note6
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
11-00
Direction
Lock
Selection
0: Allow
Forward and
Reverse
Rotation
1
1: Only Allow
Forward
Rotation
2: Only Allow
Reverse
Rotation

Other manuals for TECO F510 series