29
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
11-01
Carrier
Frequency
0: Carrier
Output
Frequency
Tuning
Inverter
KVA
*a
1: 1~16:
1~16KHz
11-02
Soft PWM
Function
Selection
0: Disable
1
*
b
1: Soft PWM
Function 1
2: Soft PWM
Function 2
11-03
Automatic
carrier
lowering
selection
0: Disable
0
1: Enable
11-04
S-curve
Time
Setting at
the Start of
Acceleration
0.00~2.50 0.20
11-05
S-curve
Time
Setting at
the End of
Acceleration
0.00~2.50 0.20
11-06
S-curve Time
Setting at the
Start of
Deceleration
0.00~2.50 0.20
11-07
S-curve Time
Setting at the
End of
Deceleration
0.00~2.50 0.20
11-08
Jump
Frequency 1
0.0~400.0 0.0
11-09
Jump
Frequency 2
0.0~400.0 0.0
11-10
Jump
Frequency 3
0.0~400.0 0.0
11-11
Jump
Frequency
Width
0.0~25.5 1.0
11-12
Manual
Energy
Saving Gain
0~100 80
11-13
Automatic
Return Time
0~120 60 *6
11-14
~
11-17
Reserved
11-18
Manual
Energy
Saving
Frequency
0.00~400.00 0.00
11-19
Automatic
Energy
Saving
Function
0: Disabled
0
1: Enabled
11-20
Filter Time
of Automatic
Energy
0~200 140
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Saving
11-21
Voltage
Upper Limit
of Energy
Saving
Tuning
0~100 100
11-22
Adjustment
Time of
Automatic
Energy
Saving
0~5000 20 *1
11-23
Detection
Level of
Automatic
Energy
Saving
0~100 10
11-24
Coefficient
of Automatic
Energy
Saving
0.00~655.34 KVA
*a
11-25
~
11-27
Reserved
11-28
Frequency
Gain of
Overvoltage
Prevention 2
1~200 100
Note4
11-29
Auto De-
rating
Selection
0: Disable
0
1: Enable
11-30
Variable
Carrier
Frequency
Max. Limit
2~16 KVA
*a
11-31
Variable
Carrier
Frequency
Min. Limit
1~16 KVA
*a
11-32
Variable
Carrier
Frequency
Proportional
Gain
00~99 00
11-33
Rise
Amount of
DC Voltage
Filter
0.1~10.0 0.1
Note4
*1
11-34
Fall Amount
of DC
Voltage
Filter
0.1~10.0 5.0
Note4
*1
11-35
Dead band
Level of DC
Voltage
Filter
0.0~99.0 10.0
Note4
*1
11-36
Frequency
Gain of OV
Prevention
0.000~1.000 0.050
Note2
*1
11-37
Frequency
Limit of OV
Prevention
0.00~400.00 5.00
Note2