44
Group 23 Pump & HVAC Function
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
23-30
Detection
Time of
Multiple
Pumps in
Parallel
Running
Start
0.0 ~ 30.0 0.0
23-31
Synchronou
s Selection
of Multiple
Pumps in
Parallel
0: Disable
1
1: Pressure
Setting and
Run/Stop
2: Pressure
Setting
3: Run/Stop
23-32 Reserved
23-33 Reserved
23-34
Tolerance
Range of
Constant
Pressure
2
Note
23-20=0 : 0.01
~ 650.00
23-20=1 :
1~100
5
Note1
23-35
Selection of
Multiple
Pumps Shift
Operation
0: No function
1: Timer
Alternately
Selected
2: Sleep Stop
Alternately
Selected
3: Timer and
Sleep Stop
Alternately
Selected
4: Multiple
Pumps Test
Mode
1
Note2
23-36
PUMP Unit
Display
0: PSI
0
Note4
1: inW
2: Bar
3: Pa
23-37
Leakage
Detection
Time
0.0~100.0 0.0 *7
23-38
Pressure
Variation of
Leakage
Detection
Restart
23-20=0 : 0.01
~ 65.00
23-20=1 : 1~10
1 *7
23-39
Pressure
Tolerance
Range of
Leakage
Detection
Restart
23-20=0 : 0.01
~ 650.00
23-20=1 :
1~100
5 *7
23-40 Reserved
23-41
Local/
Remote Key
0: Disable
1
1: Enable
23-42
Energy
Recalculatin
0: Disable
(Energy
0
Group 23 Pump & HVAC Function
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
g
A
ccumulating)
1: Enable
23-43
Electricity
Price per
kWh
0.000 ~ 5.000 0.000
23-44
Selection of
Accumulativ
e Electricity
Pulse
Output Unit
0: Disable
0
1: Unit for
0.1kWh
2: Unit for
1kWh
3: Unit for
10kWh
4: Unit for
100kWh
5: Unit for
1000kWh
23-45
Given
Modes of
Flow Meters
Feedback
0: Disable
1
1: Analog Input
2: Pulse Input
23-46
Maximum
Value of
Flow Meters
1 ~ 50000 10000
23-47
Target
Value of
Flow Meters
1 ~ 50000 5000
23-48
Maximum
Flow Value
of Feedback
0.01 ~ 99.00 80.00
23-49
Maximum
Flow
Warning
Time of
Feedback
0.0 ~ 255.0 3.0
23-50
Maximum
Flow Stop
Time of
Feedback
0.0 ~ 255.0 6.0
23-51
Minimum
Flow Value
of Feedback
0.01 ~ 99.00 10.00
23-52
Minimum
Flow
Warning
Time of
Feedback
0.0 ~ 255.0 3.0
23-53
Minimum
Flow Stop
Time of
Feedback
0.0 ~ 255.0 6.0
23-54
Detection
Function of
Low Suction
0: Disable
0
1: PID Error
Value
2: Current
3: Current and
PID Error Value
23-55
Detection
Time of Low
Suction
0 ~ 30.0 10.0

Other manuals for TECO F510 series