45
Group 23 Pump & HVAC Function
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
23-56
PID Error
Level of
Low Suction
0 ~ 30 10
23-57
Current
Level of
Low
Suction(Mot
or Rated
Current)
0 ~ 100 10
23-58
Reaction of
Low Suction
0: Disable
0
1: Warning
2: Fault
3: Fault &
Restart
23-59
Source of
HVAC
Pressure
Command
0: Set by 23-47
0
1: Set by AI
23-60
HVAC Unit
Display
0: GPM
0
Note4
1: FPM
2: CFM
3: GPH
23-66
Derating of
Current
Level
10~200 110
23-67
Derating of
Delay Time
1.0~20.0 10.0
23-68
Derating of
Frequency
Gain
1~100 90
23-69
OL4 Current
Level
10~200 120
23-70
OL4 Delay
Time
0~20.0 5.0
23-71
Maximum
Pressure
Setting
0.10~650.00
10.00
Note3
23-72
Switching
Time of
Alternation
in Parallel
0: Hour
0
Note4
1: Minute
23-73
Auxiliary
Wake-up
Selection
0: Disable
0
Note4
1: Enable
23-74
High
Pressure
Setting
0: Disable
2
Note5
1: High
Pressure
Warning
2: High
Pressure
Warning or
Error
23-75
Low
Pressure
Setting
0: Disable
0
Note5
1: Low
Pressure
Warning
2: Low
Pressure
Warning or
Group 23 Pump & HVAC Function
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Error
23-76
High Flow
Setting
0: Disable
2
Note5
1: High Flow
Warning
2: High Flow
Warning or
Error
23-77
Low Flow
Setting
0: Disable
2
Note5
1: Low Flow
Warning
2: Low Flow
Warning or
Error
23-78
Selection of
Loss
Pressure
Detection
0: Disable
0
Note5
1: Loss
Pressure
Warning
2: Low
Pressure Error
Group 24 Pump Control Function
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
24-00
Selection of
Pump
Control
Function
0: Function of 1
to 8 Pump Card
is Disabled
0
1: Fixed Modes
of Inverter
Pump: First on
and Last off;
then Stop All.
2: Fixed Modes
of Inverter Pump:
Only Stop
Inverter Pump.
3: Fixed Modes
of Inverter Pump:
First on and First
Off; then Stop
A
ll.
4: Cycle Modes
of Inverter Pump:
First on and First
Off; then Stop
A
ll.
5: Cycle Modes
of Inverter Pump:
Only Stop
Inverter Pump.
6: 1 to 3 Relay o
f
Cycle Modes of
Inverter Pump:
First on and First
off; then Stop All
7: Cycle Modes
of Inverter Pump:
First on and First
Off; then Stop
A
ll. And First
Boot Relay in