3.2 Parameter List
36
FLUXMASTER 50 INSTRUCTION MANUAL
Function F_ Function Description Unit Range
Factory
Page Note
Setting
Factory Setting 0 Factory Adjustment
Accel.Time 1 Accel.Time 0.1Sec 0.1 ~ 999S 5.0 37 *1 *3
Decel.Time 2 Decel.Time 0.1Sec 0.1 ~ 999S 5.0 37 *1 *3
Operation Mode
3
0: Forward / Stop, Reverse / Stop
1: Run/Stop, Forward / Reverse
10
~
1038
Motor Rotation
4
0: Forward
Direction: 1: Reverse
10 ~ 1038*1
V/F Pattern 5 V/F pattern setting 1 1 ~ 6 1/4 39 *2
Frequency 6 Frequency upper limit 0.1Hz 1 ~ 200 50/60Hz 40 *2 *3
Upper/Lower Limit 7 Frequency lower limit 0.1Hz 1 ~ 200 0.0Hz 40 *3
SP1 Frequency 8 SP1 frequency 0.1Hz 1 ~ 200 10Hz 40 *3
JOG Frequency 9 JOG frequency 0.1Hz 1 ~ 200 6Hz 40
Start / Stop Control 10
0: Keypad
10 ~ 1041
1:Terminal (TM2)
0: Keypad
Frequency Control 11 1:Terminal (0~10V / 0~20mA) 1 0 ~ 2 0 41
2:Terminal (4~20mA)
Carrier frequency
12 Carrier Frequency Setting 1
1 ~ 5
542*4
Control (1~10)*4
Torque Compensation 13 Torque compensation gain 0.1% 0.0 ~ 10.0% 0.0% 42 *1
Stop Method 14
0: Controlled deceleration stop
10 ~ 1043
1: Coast to stop
15 DC braking time 0.1S 0.0 ~ 25.5S 0.5S 43
DC Braking Setting 16 DC braking injection frequency 0.1Hz 1 ~ 10Hz 1.5Hz 43
17 DC braking level 0.1% 0.0 ~ 20.0% 8.0% 43
Electronic Thermal
18
Protection based on motor rated
50 ~ 100%
Overload Protection
current
1%
(0~200)
100% 44 *4
Multi-Function input terminal 1
1: Jog
19
(SP1) function
2: SP1 2 33
Multi-Function Input 3: Emergency Stop
Connection Point
Multi-Function input terminal 2
4: External Base Block
20
(RESET) function
5: Reset 5 45
6: SP2*4
1: Operating
Multi-Function Output 21 Multi-Function output terminal 2: Frequency Agreed 3 46
3: Fault