FLUXMASTER 50 INSTRUCTION MANUAL
37
Function F_ Function Description Unit Range
Factory
Note Page
Setting
Reverse Lock-Out 22
0: REV run
10
~
1046
1: REV run Lock-Out
Momentary Power
23
0: Enabled
Loss 1: Disabled
10 ~ 1046
Auto Restart 24 Number of Auto-restart times 1 0 ~ 5 0 47
Restore factory settings 25
010: Constants initialization to 50Hz system
47 *2
020: Constants initialization to 60Hz system
SP2 Frequency 26 SP2 frequency 0.1Hz 1.0 ~ 200Hz 20 48 *4
SP3 Frequency 27 SP3 frequency 0.1Hz 1.0 ~ 200Hz 30 48 *4
Power Up Start 28
0: Enable
10 ~ 1148*4
1: Disable
Software Version 29 CPU program version 48
Fault Log 30 Fault log for three faults. 48
NOTE:
*1 : Parameters that can be adjusted while running the drive.
*2 : Please refer to parameters F_25.
*3 : If the setting range is above 100, the setting unit becomes 1.
*4 : New features for CPU versions V2.1 and above.
3.3 Parameter Function Description
F_00 Factory Adjustment Parameter. Do not change.
F_01 : Acceleration Time = 0.1 ~ 999 sec
F_02 : Deceleration Time = 0.1 ~ 999 sec
1. Acceleration / Deceleration time calculation formula:
Acceleration time = F_01 x Frequency Setting
60Hz
Deceleration time = F_02 x Frequency Setting
60Hz